ClimateMaster iGate ATC32U03 Скачать руководство пользователя страница 7

7

AT C 3 2 U 0 3   C o m m u n i c a t i n g ,   P ro g r a m m a b l e   T h e r m o s t a t   -   I O M

R e v. :   N o v e m b e r   3 ,   2 0 1 7

AIRFLOW SELECTION

                                                                      CFM

HEAT STAGE 1                                              600

HEAT STAGE 2                                              750 

AUXILIARY HEAT                                          850

EMERGENCY HEAT                                      850

COOL STAGE 1                                             525

COOL STAGE 2                                             700

COOL DEHUMID 1                                        425

COOL DEHUMID 2                                        550

CONTINUOUS FAN                                       350

HEAT OFF DELAY                                           60

COOL OFF DELAY                                          30

 PREVIOUS                                             NEXT 

NOTE:

  “Motorized Valve” used here refers to a two-position 

motorized water valve, not to be confused with the modulating 
motorized water valve found in the LOOP CONFIG.

3.0  System Confi guration

Use the System Confi guration option on the start-up screen 
to adjust critical equipment settings.

The System Confi guration information will be automatically 
obtained from each communicating control in the system.

Note 1:

 The Airfl ow Selection menu (section 3.1) will not be 

present if the connected communicating control system has 
no blower.

Note 2: 

The Pump Confi guration menu (section 3.4) will 

not be present if the connected communicating control is 
confi gured for No Loop Confi guration (OTHER).

Note 3: 

The Valve Confi guration menu (section 3.5) will 

not be present if the connected communicating control is 
confi gured for No Loop Confi guration (OTHER). 

3.1 AIRFLOW 

SELECTION

Adjust the airfl ow settings for each system operating mode 
using the up/down arrow buttons.  Press the center button to 
select each item.

• Airfl ow Settings (defaults stored in control) 

valid range:  obtained from control (in 25 CFM 

increments)

•  Blower Off Delay (default 60 seconds) – 

valid 

range:  0 to 255 seconds (in 5 second increments)

NOTE 1:

  The Airfl ow Settings will only be present if the 

connected communicating control is confi gured for ECM 
blower.

NOTE 2:

  If multiple units are connected to one thermostat, 

refer to section 3.6 for unit selection.

3.2 OPTION 

SELECTION

This option allows the confi guration of heat pump options to 
be modifi ed.

Adjust the Option settings using the up/down arrow buttons.  
Press the center button to select each item.

•  Motorized Valve (defaults stored in control) – 

valid range:  Off, On “On” delays compressor start 
until the valve is fully open. 

•  Compressor ASCD (Anti-Short Cycle Delay 

(default stored in control) – 

valid range:  5 to 8 

(in 1 minute increments)

NOTE 1:

  The Compressor Anti-Short Cycle Delay setting 

provides equipment protection by forcing the compressor to 
wait a few minutes before restarting.

NOTE 2:

  If multiple units are connected to one thermostat, 

refer to section 3.6 for unit selection.

SYSTEM CONFIGURATION

AIRFLOW SELECTION

OPTION SELECTION

UNIT CONFIG                                           TE026

PUMP CONFIGURATION

SELECT OPTION   

 PREVIOUS                                          SAVE 

INSTALLER SETTINGS

THERMOSTAT CONFIG

SYSTEM CONFIG

ACCESSORY CONFIG

INPUT DEALER INFO

HUMIDITY CONFIG

TEMPERATURE CONTROL

DEMAND REDUCTION CNFG

SERVICE MODE

SETPOINT LIMITS

RESTORE DEFAULTS
DXM2                                                               3.3

ATC32U02                                                    C 1.0

SELECT OPTION   

 PREVIOUS

Содержание iGate ATC32U03

Страница 1: ...Access 6 2 2 Thermostat Configuration 6 3 0 System Configuration 7 3 1 Airflow Selection 7 3 2 Option Selection 7 3 3 Unit Configuration 8 3 4 Pump Configuration 8 3 5 Valve Configuration 9 3 6 Multi...

Страница 2: ...This page was intentionally left blank...

Страница 3: ...need not be leveled for proper operation and mark wall through 2 mounting holes 5 Drill two 3 16 in mounting holes in wall where marked Note Mounting holes on thermostat are designed to fit on a hori...

Страница 4: ...ontrol algorithm must be configured for Differential control to access the Differential settings by installer 1 1 2 HUMIDITY OFFSET If you find that the Humidity level displayed on the thermostat does...

Страница 5: ...erature at the time when Demo Mode is entered The unit will operate in heating or cooling based upon the following algorithm 1 3 3 EXITING DEMO MODE To exit demo mode remove power to the thermostat St...

Страница 6: ...onds while the thermostat is in OFF Mode 2 2 THERMOSTAT CONFIGURATION Upon initial power up the communicating thermostat will prompt the installer for the thermostat configuration settings Model numbe...

Страница 7: ...e center button to select each item Airflow Settings defaults stored in control valid range obtained from control in 25 CFM increments Blower Off Delay default 60 seconds valid range 0 to 255 seconds...

Страница 8: ...OP CONFIG VS PUMP SELECT OPTION PREVIOUS SAVE 3 4 PUMP CONFIGURATION vFlow vs internal flow control pump can be controlled either through temperature differential Delta T or can be set to specific spe...

Страница 9: ...figuration instructions MODULATING VALVE CONFIGURATION OFF POSITION 0 0 VALVE CONTROL DELTA T HEATING DELTA T 7 F COOLING DELTA T 10 F MAXIMUM HEAT LWT 80 F MINIMUM COOL LWT 40 F PREVIOUS SELECT For c...

Страница 10: ...ts Calendar Time default Off valid range Off 3 to 24 months in 3 month increments 4 3 UV LAMP This feature displays an alert to remind the user to change the UV lamps after the selected time has passe...

Страница 11: ...ershooting the temperature setpoint adjust the Anticipator value up to reduce thermostat sensitivity If the thermostat is undershooting the temperature setpoint adjust the Anticipator value down to in...

Страница 12: ...the center button to save changes Smart Heat Staging default Off options OFF 5 120 minutes in 5 minute increments 7 6 ELECTRIC HEAT LOCKOUT Electric heat lockout keeps electric heat turned off if the...

Страница 13: ...3 1 ON FACTORY SETTING 2 OFF HWG TEST OFF 3 OFF HWG SP 125 4 OFF HWG DISABLED JW3 LT1 SETTING WELL PREVIOUS 9 3 DIPSWITCH CONFIGURATION Dipswitch Configuration mode allows the service personnel to vie...

Страница 14: ...9 7 9 4 4 Configuration Conditions Displays the status of all dipswitch settings that were recorded at the time the fault occurred NOTE If multiple units are connected to one thermostat refer to secti...

Страница 15: ...onnected directly to the ATC thermostat or connected to one another in series as shown by the figure below CONTROL DIAGNOSTICS TT026 S N 1 2 3 4 TT026 S N 5 6 7 8 TT038 S N 9 0 1 2 PREVIOUS SELECT TT0...

Страница 16: ...imateMaster s opinion or commendation of its products ClimateMaster Inc 2012 97B0055N03 7300 S W 44th Street Oklahoma City OK 73179 Phone 405 745 6000 Fax 405 745 6058 climatemaster com Rev November 3...

Отзывы: