Flow Controller 3
R e v. : F e b u r a r y 9 , 2 0 1 6
Tw
o Units with One Flow Controller
NOTES: 1. Piping is shown schematically
. Actual pipe diameter and layout must be determined before installation.
2. Pressure drop calculation must be made to verify that Flow Controller can deliver design flow rate when both units are oper
ating.
3. Hose kits of longer than 10 ft. (3 meters) one way should not be used. PE pipe or SCH80 PVC should be used for lengths gre
ater than 10 ft. (3 meters).
4.
All units must include P/T
ports for flow rate measure and balancing.
5. Use optional field-installed loop pump slaving relay (part #
APSM) to wire both units to the Flow Controller pump(s).
Heat Pump
Heat Pump
Flow
Controller
Field-supplied
full-port ball valv
e
for balancing
Each heat pump must include P/T
ports to verify flow rates
LW
T
EWT
LW
T
EWT
Heat Pump
Heat Pump
Flow
Controller
Wa
ter Out
Wa
ter In
Wa
ter Out
Wa
ter In
Figure 7a: Parallel Unit Piping 1
Piping Installation