ClimateMaster Flow Controller 3 Скачать руководство пользователя страница 14

Flow Controller 3

R e v. : F e b u r a r y   9 , 2 0 1 6

14

G e o t h e r m a l   H e a t   P u m p   S y s t e m s

Antifreeze Selection

Table 4: Antifreeze Percentages by Volume

NOTICE:

 DO NOT use automotive windshield washer 

fluid as antifreeze. Most washer fluid contains 

chemicals that will cause foaming. 

� 

WARNING! 

WARNING!

 Always use properly marked vehicles (D.O.T. 

placards), and clean/suitable/properly identified containers 

for handling flammable antifreeze mixtures. Post and 

advise those on the jobsite of chemical use and potential 

dangers of handling and storage.

� 

CAUTION! 

CAUTION!

 Always obtain MSDS safety sheets for all 

chemicals used in ground loop applications including 

chemicals used as antifreeze.

Methanol - Methanol or wood alcohol is considered toxic in 

any form, has good heat transfer, low to mid price, flammable 

in concentrations greater than 25%, non-corrosive, and low 

viscosity. Methanol has delivered outstanding performance in 

earth loops for over 20 years. Its only drawbacks are toxicity 

and flammability. Although methanol enjoys widespread 

consumer use as a windshield washer fluid in even higher 

concentrations, some local codes may limit its use in earth 

loops. To increase safety, a premixed form should be used on 

the jobsite to increase the safety factor. Pure methanol can be 

purchased from any chemical supplier. 

Ethanol - Ethanol or grain alcohol exhibits good heat 

transfer (slightly less than methanol), higher price, and is 

flammable in concentrations greater than 10%. Ethanol 

is generally non-corrosive and has medium viscosity. 

Ethanol in its pure form is considered nontoxic and shows 

promise as a geothermal heat transfer fluid. However the 

U.S. Bureau of Alcohol, Tobacco, and Firearms (ATF) limit 

its distribution. All non-beverage ethanol is required to be 

denatured and rendered unfit to drink. Generally this is done 

by adding a small percentage of toxic substances such 

as methanol, benzene, or gasoline as a denaturant. Many 

of these denaturants are difficult to identify by the casual 

user and many are not compatible with polyethylene pipe. 

Only denatured ethanol can be purchased for commercial 

use. The use of ethanol is not recommended because of 

the unknown denaturants included in the solution, and their 

possible toxicity and damage resulting to polyethylene 

piping systems. Denaturing agents that are petroleum based 

can damage polyethylene pipe.

Ethylene glycol - Generally non-corrosive, expensive, 

medium heat transfer, considered toxic. Its toxicity has 

prevented its widespread use in the ground source industry 

in spite of its widespread use in traditional water-source 

heat pump applications. Ethylene glycol is not currently 

recommended as ground-source antifreeze.

Propylene glycol - Nontoxic, non-corrosive, expensive, hard to 

handle when cold, poorest heat transfer, has formed “slime-

type” coatings inside pipe. Poor heat transfer has required 

its removal in some systems. Propylene glycol is acceptable 

in systems anticipating loops temperatures no colder than 

40°F [4.4°C]. These systems typically use antifreeze because 

of low ambient conditions (outside plumbing or cooling 

tower, etc.). When loop temperatures are below 40°F [4.4°C], 

the fluid becomes very difficult to pump and heat transfer 

characteristics suffer greatly. Only food grade propylene glycol 

is recommended to prevent the corrosion inhibitors (often 

present in other mixtures) from reacting with local water and 

‘coming out’ of solution to form slime type coatings inside heat 

exchangers and thus hinder heat transfer. If propylene glycol 

must be used (e.g. code requirements), careful consideration 

of loop Reynolds numbers, pump selection and pressure drop 

must be considered.

Potassium acetate - Nontoxic, good heat transfer, high price, 

non-corrosive with added inhibitors, low viscosity. Due to its 

low surface tension, Potassium Acetate has been known to 

leak through mechanical fittings and certain thread sealants. 

A variant of the salt family, it can be extremely corrosive when 

exposed to air. Potassium Acetate is not recommended in 

ground-source applications due to the leaking and (ultimately) 

corrosion problems associated with it. 

Contact the Technical Services Department if you have any 

questions as to antifreeze selection.

Type

Minimum Temperature  

for Low Temperature Protection

10°F 

[-12.2°C]

15°F 

[-9.4°C]

20°F 

[-6.7°C]

25°F 

[-3.9°C]

Methanol

Propylene Glycol

Ethanol*

21%

29%

23%

17%

24%

20%

13%

18%

16%

8%

12%

11%

* Must not be denatured with any petroleum based product

Содержание Flow Controller 3

Страница 1: ...Mounting 4 Piping Installation 5 Electrical Wiring 9 Flushing the Earth Loop 10 Antifreeze Selection 13 Antifreeze Charging 15 Low Temperature Cutout Selection 16 Flow Controller Pump Curves 17 Pump...

Страница 2: ...Flow Controller 3 R ev F e bu rary 9 2016 2 Geothermal Heat Pump Systems This page has intentionally been left blank...

Страница 3: ...or two Grundfos pump models UP26 99 or UP26 116 are available for a variety of unit flow rates and loop layouts Flow Controllers are designed for systems that require water flow rate of up to 20 U S G...

Страница 4: ...ting Stud Wall Mounting on stud wall with or without drywall can be accomplished by using the two supplied lag bolts through the top and bottom center holes directly into the studs as shown in Figure...

Страница 5: ...D 1 2 12 7 mm wall 1 IPS PE 1 1 4 31 8 mm ID 1 2 12 7 mm wall 1 1 4 IPS PE 1 5 8 41 3 mm ID 1 2 12 7 mm wall 2 IPS PE 2 3 8 60 3 mm ID 1 2 12 7 mm wall Table 2 Typical Piping Insulation Materials AFC4...

Страница 6: ...s typically connected using the hose kit AHK5EC which contains all fittings necessary for connection between the Flow Controller and the unit as shown in Figure 5 In multiple unit systems PE piping ma...

Страница 7: ...should not be used PE pipe or SCH80 PVC should be used for lengths greater than 10 ft 3 meters 4 All units must include P T ports for flow rate measure and balancing 5 Use optional field installed lo...

Страница 8: ...lose enough to unit to maintain short approx 10 ft 3m hose kit from Flow Controller to unit 4 All units must include P T ports for flow rate measure and balancing Multiple Units on Common Loop Field P...

Страница 9: ...e phase voltage Pumps are fused through a pair of circuit breakers in the unit control box See electrical table for Flow Controller characteristics The pump slaving module is designed to allow two uni...

Страница 10: ...least a 1 5 hp 1 1kW pump is needed to achieve adequate flow velocity in the loop to purge air and dirt particles from the loop itself Antifreeze solution is used in most areas to prevent freezing All...

Страница 11: ...uously mixed back into the fluid Surges of 50 psi 345 kPa can be used to help purge air pockets by simply shutting off the return valve going into the flush cart reservoir This process dead heads the...

Страница 12: ...seasons and pressures will be higher in the winter months than during the cooling season This fluctuation is normal and should be considered when charging the system initially Unhook the flush cart fr...

Страница 13: ...imum entering loop temperatures drop below 40 F 4 4 C or where piping will be routed through areas subject to freezing antifreeze is needed Alcohols and glycols are commonly used as antifreeze solutio...

Страница 14: ...anol is not recommended because of the unknown denaturants included in the solution and their possible toxicity and damage resulting to polyethylene piping systems Denaturing agents that are petroleum...

Страница 15: ...through both the unit and the loop and flush until fluid is homogenous and mixed It is recommended to run the unit in the heating and cooling mode for 15 20 minutes each to temper the fluid temperatur...

Страница 16: ...ent internal damage to the port Use same gauge and thermometer to determine the differential in pressure and temperature Earth Loop Pressure The earth loop must have a slight positive pressure to oper...

Страница 17: ...6 17 18 19 20 21 22 23 24 25 26 27 28 29 30 Flow Rate Head ft kPa 1 Grundfos 26 99 2 Grundfos 26 99 2 Grundfos 26 116 3 Grundfos 26 99 0 06 0 13 0 19 0 25 0 32 0 38 0 44 0 50 0 57 0 63 0 69 0 76 0 82...

Страница 18: ...e with new pump insuring no foreign material has been introduced and evenly install the four Allen head mounting bolts 5 Place garden hose supply and return on flush ports as shown in Figure 12 and op...

Страница 19: ...to be more forgiving of operator skill Joints are frequently required in difficult trench connections and the smaller socket fusion iron is more mobile Operators will have less of a tendency to cut co...

Страница 20: ...per kW minimum In larger systems 2 5 to 2 7 gpm per ton 2 41 to 2 90 l m per kW is adequate in most cases Selecting pumps to attain exactly 3 gpm per ton 3 23 l m per kW is generally not cost effectiv...

Страница 21: ...uce pressure drop problems In general 2 feet of head 6 kPa pressure drop is allowed for all earth loop fittings which would include 10 12 elbows for inside piping to the Flow Controller This allows a...

Страница 22: ...ails common loop cross sections used in horizontal loops Actual number of circuits used in each trench will vary depending upon property size Use GeoDesigner software to determine the best layout Vert...

Страница 23: ...is not intended for commercial loop design Figure 16 Typical Horizontal Loop Configurations Seal and protect the entry point of all earth coupling entry points into the building using conduit sleeves...

Страница 24: ...when all loops are assembled before backfilling and pipe burial Closed Loop Installation Figure 18 Typical Pond Lake Loop Configurations Building Entry Figure 19 Slab on Grade Entry Detail Figure 20 R...

Страница 25: ...1 40 1 86 7434 0 49 1 19 5946 12 26 82 6 63 14655 9 22 4 23 11702 3 08 2 66 9281 1 63 2 03 8110 0 57 1 30 6486 13 30 84 7 18 15876 10 60 4 58 12677 3 54 2 88 10054 1 87 2 20 8786 0 65 1 41 7027 14 12...

Страница 26: ...9 22 3 87 6287 3 10 2 44 4986 1 64 1 86 4357 0 58 1 19 3485 12 30 94 6 63 8588 10 70 4 23 6858 3 59 2 66 5439 1 91 2 03 4753 0 67 1 30 3801 13 35 51 7 18 9304 12 27 4 58 7430 4 11 2 88 5892 2 18 2 20...

Страница 27: ...2 44 5272 1 62 1 86 4607 0 57 1 19 3685 12 30 46 6 63 9082 10 53 4 23 7252 3 53 2 66 5752 1 87 2 03 5026 0 66 1 30 4020 13 34 97 7 18 9839 12 08 4 58 7857 4 05 2 88 6231 2 15 2 20 5445 0 75 1 41 4355...

Страница 28: ...01 1 47 1 86 6380 0 51 1 19 5103 12 27 90 6 63 12577 9 61 4 23 10043 3 21 2 66 7965 1 70 2 03 6960 0 59 1 30 5567 13 32 07 7 18 13625 11 04 4 58 10880 3 69 2 88 8629 1 95 2 20 7540 0 68 1 41 6031 14 1...

Страница 29: ...5 3 4 6 5 0 2 0 1 6 1 3 2 7 9 1 3 6 1 1 5 0 0 4 6 5 2 8 6 2 8 6 1 3 0 3 9 2 5 6 3 9 4 3 1 9 0 8 3 9 9 5 4 3 1 1 7 1 3 8 8 0 2 2 7 1 7 5 0 8 4 1 7 2 4 8 2 6 8 1 6 2 0 1 3 6 8 3 6 8 3 1 3 3 0 4 4 3 6 3...

Страница 30: ...5 99 3 17 7308 5 79 3 17 8363 10 7 02 3 52 8997 8 09 3 52 5095 7 20 3 52 8115 6 96 3 52 9286 11 8 29 3 87 9892 9 56 3 87 5602 8 51 3 87 8922 8 23 3 87 10210 12 9 65 4 23 10812 11 13 4 23 6123 9 91 4 2...

Страница 31: ..._____________________________________________________________________________________ Permit number _______________ Owner s preference on location of loop __________________________ __________________...

Страница 32: ...ls or rating labels have been removed or defaced 5 Products on which payment to CM or to the owner s seller or installing contractor is in default 6 Products which have not been installed and maintain...

Страница 33: ...33 Flow Controller 3 Rev Febur ary 9 2 0 1 6 Notes...

Страница 34: ...s and do not form the basis of any bargain between the parties but are merely ClimateMaster s opinion or commendation of its products ClimateMaster Inc 2006 97B0015N01 7300 S W 44th Street Oklahoma Ci...

Отзывы: