Unit & System Checkout

LT1
LT2

LT1
LT1
LT2
LT2

Short test pins together 

to enter Test Mode and 

speed-up timing and delays 

for 20 minutes.

Figure 5: Test Mode Pins

CXM BOARD

BEFORE POWERING SYSTEM, please check the following:
UNIT CHECKOUT

  Balancing/Shutoff Valves: Ensure all isolation valves 

are open, water control valves wired and open or coax 

may freeze and burst.

q

  Line Voltage and Wiring: Ensure Voltage is within an 

acceptable range for the unit and wiring and fuses/

breakers are properly sized. Low voltage wiring is 

complete.

q

  Unit Control Transformer: Ensure transformer has 

properly selected control voltage tap. 208-230V units 

are factory wired for 208V operation unless specified 

otherwise.

q

  Entering Water: Ensure entering water temperatures are 

within operating limits of Table 6.

q

  Low Water Temperature Cutout: Verify low water 

temperature cut-out on CXM/DXM is properly set.

q

  Water Flow Balancing: Verify inlet and outlet water 

temperatures  on both Load and source are recorded 

for each heat pump upon startup. This check can 

eliminate nuisance trip outs and high velocity water 

flows that can erode heat exchangers.

q

  Unit Controls: Verify CXM or DXM field selection 

options are proper and complete.

SYSTEM CHECKOUT

q

  System Water Temperature: Check load and source 

water temperature for proper range and also verify 

heating and cooling setpoints for proper operation.

q

  System pH: System water pH is 6 - 8.5. Proper pH 

promotes longevity of hoses and fittings.

q

  System Flushing: Verify all hoses are connected end 

to end when flushing to ensure debris bypasses unit 

heat exchanger and water valves etc. Water used in 

the system must be potable quality initially and clean 

of dirt, piping slag, and strong chemical cleaning 

agents. Verify all air is purged from the system. Air 

in the system can cause poor operation or system 

corrosion.

q

  Cooling Tower/Boiler: Check equipment for proper 

setpoints and operation.

q

  Standby Pumps: Verify the standby pump is properly 

installed and in operating condition.

q

  System Controls: Verify system controls function and 

operate in the proper sequence.

q

  Low Water Temperature Cutout: Verify low water 

temperature cut-out controls are provided for the 

outdoor portion of the loop or operating problems 

will occur.

q

  System Control Center: Verify control center and 

alarm panel for proper setpoints  

and operation.

q

  Strainers: Verify 20 mesh (841 micron) [0.84mm] 

strainers are installed in load and source water 

piping. Confirm maintenance schedule for strainers.

q

  Miscellaneous: Note any questionable aspects of   

the installation.

 

WARNING!

 

WARNING! 

Verify ALL water controls are open and allow 

water flow prior to engaging the compressor.  Freezing of the 

coax or water lines can permanently damage the heat pump.

 

WARNING!

 

WARNING! 

To avoid equipment damage, DO NOT leave 

system filled in a building without heat during the winter 

unless antifreeze is added to system water.  Condenser 

coils never fully drain by themselves and will freeze unless 

winterized with antifreeze.

Note: The manufacturer strongly recommends all piping 

connections, both internal and external to the unit, be 

pressure tested by an appropriate method prior to any 

finishing of the interior space or before access to all 

connections is limited. Test pressure may not exceed 

the maximum allowable pressure for the unit and all 

components within the water system. The manufacturer 

will not be responsible or liable for damages from water 

leaks due to inadequate or lack of a pressurized leak 

test, or damages caused by exceeding the maximum 

pressure rating during installation. 

WARNING!

 Polyolester Oil, commonly known as POE oil, is 

a synthetic oil used in many refrigeration systems including 

those with HFC-410A refrigerant. POE oil, if it ever comes 

in contact with PVC or CPVC piping, may cause failure of 

the PVC/CPVC. PVC/CPVC piping should never be used 

as supply or return water piping with water source heat 

pump products containing HFC-410A as system failures and 

property damage may result.

 

WARNING!

 

Содержание EarthPure Tranquility TMW Series

Страница 1: ...11 Ground Water Heat Pump Applications 12 13 Water Quality Standards 12 Ground Loop Heat Pump Applications 14 15 Electrical Line Voltage 16 Electrical Accessories 17 Electrical Line Voltage 18 Electri...

Страница 2: ...C LI MATE MASTER WATER SOURCE HEAT PUMPS Tranquility Water to Water TMW Series Rev March 10 2021 ClimateMaster Water Source Heat Pumps 2 This Page Intentionally Left Blank...

Страница 3: ...TEMPERATURE MODELTYPE W WATERTO WATER HEATPUMP CONFIGURATION UNIT SIZE 036 E F G H REVISION LEVEL A CURRENT VOLTAGE CONTROLS CABINET INSULATION 1 COMMERCIALEXTENDED RANGE HOT WATER GENERATOR OPTIONS T...

Страница 4: ...ates a potentially hazardous situation which if not avoided could result in death or serious injury CAUTION Indicates a potentially hazardous situation or an unsafe practice which if not avoided could...

Страница 5: ...each unit The installation site chosen should include adequate service clearance around the unit Before unit start up read all manuals and become familiar with the unit and its operation Thoroughly ch...

Страница 6: ...es 400 2 758 Model TMW036 TMW060 TMW120 TMW170 TMW340 Compressor qty Scroll 1 Scroll 2 Scroll 1 Scroll 2 Factory Charge R410A lbs kg Circuit 4 5 2 04 5 5 2 49 5 5 2 49 14 9 6 75 14 9 6 75 Indoor Load...

Страница 7: ...L K 1 0 2 5 cm 1 2 3 4 5 6 J H G F E D 1 3 5 Required Service Access Optional Service Access Required Service Acce Optional Service Access B C A 1 8 4 6 cm 1 3 3 3 cm 2 7 6 9 cm 1 0 2 5 cm 3 Ft 3 Ft N...

Страница 8: ...KO 4 5 114 2 IPT Water Connections 15 0 381 5 4 138 21 0 533 Fault Run Lights 64 5 1638 Left Side View Front View Top View Load Source Side Refrig Circuit Access Panel Front Compressor Access Panel E...

Страница 9: ...ng the flared surfaces of the joint PIPING INSTALLATION TMW Unit Location These units are not designed for outdoor installation Locate the unit in an INDOOR area that allows enough space for service p...

Страница 10: ...fittings at one end to prevent kinking during installation Refer to Figure 1 for an illustration of a Supply Return Hose Kit Male adapters secure hose assemblies to the unit and risers Install hose as...

Страница 11: ...ecommends 2 5 gpm per ton Air Pad or Extruded polystyrene insulation board Unit Power Disconnect Pressure Tank Flow Regulator Water Control Valve P T Plugs Water Out Shut Off Valve Boiler Drains Water...

Страница 12: ...sulfate compounds All 0 5 ppm Maximum Maximum Allowable at maximum water temperature Chloride Levels 10 C 24 C 38 C Copper Cupronickel 20ppm NR NR 150 ppm NR NR 304 SS 400 ppm 250 ppm 150 ppm 316 SS...

Страница 13: ...UTION Many units are installed with a factory or field supplied manual or electric shut off valve DAMAGE WILL OCCUR if shut off valve is closed during unit operation A high pressure switch must be ins...

Страница 14: ...Antifreeze Percentages by Volume Antifreeze In areas where minimum entering loop temperatures drop below 40 F 5 C or where piping will be routed through areas subject to freezing anti freeze is needed...

Страница 15: ...ze 208 Volt Operation All 208 230 Volt units are factory wired for 208 Volt The transformers may be switched to 230V operation as illustrated on the wiring diagram by switching the Red 208V and the Or...

Страница 16: ...T1 jumper should be clipped when antifreeze is used Model Voltage Code Volatge Voltage Min Max Compressor Total Unit FLA Min Circuit Amps SCCR rms Symetrical SCCR Volts Maximum Max Fuse HACR Qty RLA L...

Страница 17: ...HP Switch Circuit 1 VR3 NO RED RED 2 4 Refrigerant HP Switch Circuit 2 VR3 NO RED RED 6 8 Refrigerant HP Switch Circuit 1 VR3 NO RED RED 2 4 Refrigerant HP Switch Circuit 2 VR3 NO RED RED Coil Valve R...

Страница 18: ...uit to minimize vibration and sound transmission to the building 208 Volt Operation All 208 230 Volt units are factory wired for 208 Volt The transformers may be switched to 230V operation as illustra...

Страница 19: ...e temperature when using antifreezes It should be noted that the extended range option should be specified to operate the TMW Series at entering water temperatures below 60 F Figure 6a TMW036 060 Low...

Страница 20: ...460 60 3 575 60 3 96B0224N02 208 230 60 1 TMW060 ONLY TMW120 96B0225N02 208 230 60 1 CXM 96B0225N03 208 230 60 3 460 60 3 575 60 3 96B0225N05 208 230 60 1 DXM 96B0225N06 208 230 60 3 460 60 3 575 60...

Страница 21: ...Tranquility Water to Water TMW Series Rev March 10 2021 TH E SMART SOLUTION FOR ENERGY EFFICI E N CY climatemaster com 21 Typical Wiring Diagram Three Phase TMW170 Units with CXM Controller...

Страница 22: ...MATE MASTER WATER SOURCE HEAT PUMPS Tranquility Water to Water TMW Series Rev March 10 2021 ClimateMaster Water Source Heat Pumps 22 Typical Wiring Diagram Three Phase TMW340 Units with CXM MPC Contro...

Страница 23: ...Tranquility Water to Water TMW Series Rev March 10 2021 TH E SMART SOLUTION FOR ENERGY EFFICI E N CY climatemaster com 23 Typical Wiring Diagram Three Phase TMW340 Units with CXM Controller...

Страница 24: ...I MATE MASTER WATER SOURCE HEAT PUMPS Tranquility Water to Water TMW Series Rev March 10 2021 ClimateMaster Water Source Heat Pumps 24 Typical Wiring Diagram Three Phase TMW340 Units with DXM Controll...

Страница 25: ...Tranquility Water to Water TMW Series Rev March 10 2021 TH E SMART SOLUTION FOR ENERGY EFFICI E N CY climatemaster com 25 Typical Wiring Diagram Three Phase TMW170 Units with DXM Controller...

Страница 26: ...C LI MATE MASTER WATER SOURCE HEAT PUMPS Tranquility Water to Water TMW Series Rev March 10 2021 ClimateMaster Water Source Heat Pumps 26 Typical Wiring Diagram Three Phase TMW170 Units with CXM CE...

Страница 27: ...Tranquility Water to Water TMW Series Rev March 10 2021 TH E SMART SOLUTION FOR ENERGY EFFICI E N CY climatemaster com 27 Typical Wiring Diagram Three Phase TMW170 Units with DXM CE...

Страница 28: ...MATE MASTER WATER SOURCE HEAT PUMPS Tranquility Water to Water TMW Series Rev March 10 2021 ClimateMaster Water Source Heat Pumps 28 Typical Wiring Diagram Three Phase TMW340 Units with CXM Controlle...

Страница 29: ...Tranquility Water to Water TMW Series Rev March 10 2021 TH E SMART SOLUTION FOR ENERGY EFFICI E N CY climatemaster com 29 Typical Wiring Diagram Three Phase TMW340 Units with DXM Controller CE...

Страница 30: ...I MATE MASTER WATER SOURCE HEAT PUMPS Tranquility Water to Water TMW Series Rev March 10 2021 ClimateMaster Water Source Heat Pumps 30 Typical Wiring Diagram Three Phase TMW120 Units with CXM Controll...

Страница 31: ...Tranquility Water to Water TMW Series Rev March 10 2021 TH E SMART SOLUTION FOR ENERGY EFFICI E N CY climatemaster com 31 Typical Wiring Diagram Single Phase TMW036 Units...

Страница 32: ...Options Note In the following field configuration options jumper wires should be clipped ONLY when power is removed from the CXM control Water coil low temperature limit setting Jumper 3 JW3 LT1 Low...

Страница 33: ...pen LT1 Fault Slow Flash Flashing Code 4 Open LT2 Fault Slow Flash Flashing Code 5 Open CO Fault Slow Flash Flashing Code 6 Open Over Under Voltages Slow Flash Flashing Code 7 Open closed after 15 min...

Страница 34: ...ides selection of boilerless changeover temperature set point Note that the LT1 thermistor is sensing refrigerant temperature between the coaxial heat exchanger and the expansion device TXV or cap tub...

Страница 35: ...ec pause 2 quick flashes 10 sec pause etc Low pressure switch The low pressure switch must be open and remain open for 30 continuous seconds during on cycle to be recognized as a low pressure fault If...

Страница 36: ...ult LED will flash Code 1 The yellow test LED will turn on when in test mode CXM DXM Control Start up Operation The control will not operate until all inputs and safety controls are checked for normal...

Страница 37: ...at the lowest point in the system Adjust the make up water replacement rate to equal the rate of bleed 7 Refill the system and add trisodium phosphate in a proportion of approximately one pound per 15...

Страница 38: ...corrosion q Cooling Tower Boiler Check equipment for proper setpoints and operation q Standby Pumps Verify the standby pump is properly installed and in operating condition q System Controls Verify s...

Страница 39: ...epair of the equipment WARNING WARNING When the disconnect switch is closed high voltage is present in some areas of the electrical panel Exercise caution when working with energized equipment WARNING...

Страница 40: ...16 60 91 113 203 207 12 18 12 18 8 17 70 95 124 204 216 16 34 12 18 9 19 80 107 128 212 217 33 35 12 18 9 20 80 1 5 50 104 111 343 348 9 14 18 25 19 28 7 14 60 121 132 355 360 9 14 18 25 7 16 70 138 1...

Страница 41: ...0 108 474 488 6 11 7 11 4 16 2 3 60 95 102 215 228 6 13 7 11 6 12 7 18 80 98 106 299 313 6 13 7 11 6 18 90 99 108 329 341 6 13 7 11 6 18 100 102 110 384 401 6 13 7 11 6 17 120 106 114 475 491 6 13 7 1...

Страница 42: ...erioration of iron or galvanized piping or components in the system or open cooling towers requiring heavy chemical treatment and mineral buildup through water use Should periodic coil cleaning be nec...

Страница 43: ...amage or insuf cient performance as a result of insuf cient or incorrect system design or the improper application installation or use of CM s products or 14 Electricity or fuel costs or any increases...

Страница 44: ...result of insuf cient or incorrect system design or the improper application of CM s products CM is not responsible for 1 The costs of any uids refrigerant or other system components or associated lab...

Страница 45: ...mize troubleshooting and costly system failures complete the following checks and data entries before the system is put into full operation Temperatures F or C Antifreeze _____ Type of Antifreeze ____...

Страница 46: ...er Out Temp 12 Load Water In Pres 13 Load Water Out Pres 13a Press Drop 13b Flow Rate GPM l s Heat of Extraction Absorption or Heat of Rejection HE or HR Flow Rate x Temp Diff x Fluid Factor s e t o N...

Страница 47: ...Tranquility Water to Water TMW Series Rev March 10 2021 TH E SMART SOLUTION FOR ENERGY EFFICI E N CY climatemaster com 47 Notes...

Страница 48: ...ted 6 12 20 Decoder Updated 6 11 20 Unit Physical and Electrical Data Updated 06 10 20 Format All Pages Updated 07 14 17 Potable Water Statement Updatedp 04 15 16 Text Updated 10 16 15 Wiring Diagram...

Отзывы: