Electrical – Line Voltage
All field installed wiring, including electrical ground, must
comply with the National Electrical Code as well as all
applicable local codes.
Refer to the unit wiring diagrams for fuse sizes and a
schematic of the field connections which must be made
by the installing (or electrical) contractor.
Consult the unit wiring diagram located on the inside of the
compressor access panel to ensure proper electrical hookup.
All final electrical connections must be made with a
length of flexible conduit to minimize vibration and sound
transmission to the building.
208 Volt Operation -
All 208-230 Volt units are factory
wired for 208 Volt. The transformers may be switched to
230V operation as illustrated on the wiring diagram. By
switching the Red (230V) and the Orange (208V) at the
contactor terminal L2.
Capacitor
Transformer
CXM Control
Circ Brkr
Contactor -CC
Low Voltage
Connector
CB
HWG PB2
T2
T1
Rev .: 01/21/09B
Unit Power Supply
See electrical table for
wire and breaker size
L2
L1
External Pump
Power Supply
See electrical table for
wire and breaker size
Grnd
Loop PB1
T2 T1
Install HWG Pump
Power after insuring
water is in HWG circuit
Yellow
Grnd
L2
L3
L1
Contactor -C
Grnd
Capacitor
Transformer
CXM Control
Circ Brkr
Contactor -CC
Low Voltage
Connector
CB
HWG PB2
T2
T1
Rev .: 01/21/09B
Unit Power Supply
See electrical table for
wire and breaker size
L2
L1
External Pump
Power Supply
See electrical table for
wire and breaker size
Grnd
Loop PB1
T2 T1
Install HWG Pump
Power after insuring
water is in HWG circuit
Yellow
Grnd
L2
L3
L1
Contactor -C
Grnd
ALL wiring diagrams available at climatemaster.com
TMW120 Series Line Voltage Field Wiring Commercial Class
TMW036-060 Series Line Voltage Field Wiring Commercial Class (3 phase shown)