C L I M AT E M A S T E R WAT E R - S O U R C E H E AT P U M P S
Tranquility
®
Water-to-Water (TMW) Series
R e v. : M a r c h 1 0 , 2 0 2 1
C l i m a t e M a s t e r Wa t e r-S o u rc e H e a t P u m p s
6
Unit Physical Data
Dual isolated compressor mounting
Balanced port expansion valve (TXV)
Insulated Source and Load Water Coils standard
Insulated Refrigerant Circuit standard
Compressor on (green) and fault (red) light
Unit Maximum Water Working Pressure
Options
Max Working Pressure PSIG [kPa]
Base Unit
300 [2,068]
Motorized Valves
400 [2,758]
Model
TMW036
TMW060
TMW120
TMW170
TMW340
Compressor (qty)
Scroll (1)
Scroll (2)
Scroll (1)
Scroll (2)
Factory Charge R410A (lbs) [kg] / Circuit
4.5 [2.04]
5.5 [2.49]
5.5 [2.49]
14.9 [6.75]
14.9 [6.75]
Indoor / Load Water connection sizes FPT (in)
3/4”
1”
1-1/2”
2”
Outdoor / Source Water connection Size FPT (in)
3/4”
1”
1-1/2”
2”
HWG Water In/Out IPT (in)
1/2”
N/A
Weight - Operating (lbs) [kg]
348 [158]
360 [163]
726 [329]
790 [358]
1330 [603]
Weight - Shipping (lbs) [kg]
373 [169]
385 [175]
770 [349]
800 [363]
1340 [608]
Water Volume (Source)
Gallons (LIters)
0.96 (3.64)
1.33 (5.04)
2.65 (10.02)
3.50 (13.27)
6.72 (25.44)
Dual isolated compressor mounting
Balanced port expansion valve (TXV)
Compressor on (green) and fault (red) light