Multi-Appliance Comfort Control
Controls- Installation / Setup / Commissioning
SETTING UP THE CONTROLS – DUCTED EVAPORATIVE AIR CONDITIONING
S
ETTING
M
INIMUM
F
AN
S
PEED
1.
Using the
MANUAL/AUTO
button set the unit to MANUAL
2.
Using the
HEAT/COOL/FRESH AIR
button set the unit to
COOL FRESH AIR
3.
Adjust the fan speed to the minimum fan speed level and
press ENTER.
4.
Press the
ENTER
and
ECONOMY/ BOOST
buttons together
for approximately 10 seconds pressing the ENTER button first.
5.
The words FAN SPEED and a number under the room
temperature will flash.
6.
Adjust minimum fan speed to a number suitable to the system
design. Ensure that the motor does not over-temp if setting the
fan speed lower.
7.
Press
ENTER
to keep new fan speed.
S
ETTING
M
AXIMUM
F
AN
S
PEED
Maximum fan speed can only be access after the minimum fan
speed has been checked.
1.
Using the
MANUAL/AUTO
button set the unit to MANUAL.
2.
Using the
HEAT/COOL/FRESH AIR
button set the unit to
COOL FRESH AIR.
3.
Using the
ECONOMY/BOOST
button set the unit to BOOST.
Press ENTER.
4.
Press the
ENTER
and
ECONOMY/ BOOST
buttons together
for approximately 10 seconds pressing the ENTER button first.
5.
The words FAN SPEED and a number under the room
temperature will flash.
6.
Adjust maximum fan speed to 35 or a number to suit the
system design.
7.
Press
ENTER
to keep new fan speed.
Setting the fan speeds to a low setting should be completed by an
authorised installer / service technician. Motor warranty may be
voided for incorrect settings.
Comfort Control - PNE
Page 43