ClimaCheck Gateway NX400 Hardware Manual
–
2020-03-26 Page 17 of 41
If this is the first setup
, “
T1 Sensor not conf
” appears in the display, if sensors are already
configured these will be listed.
•
With the up and down arrows go to the position you want to save a sensor to
•
Press SEL
•
“
TX New
=xxxxxx OK” is showed in the display (
Were TX is the position and xxxxxx is the
id number of the sensor)
•
Confirm with OK
, “S
-
RID Saved” appears for 2 seconds
•
Temperature reading and ID is appearing in the display “T
X=XX.X
ID=xxxxxx”
•
Press ESC 4 times to go back to the main menu or start from the top to connect another
sensor.
If “No new s
-
r found” appears while setting up a new sensor the
NX400 cannot find any sensor on
the bus that is not already configured, check connection and make sure the sensor has not been
connected already.
3.7.3
Replace a 1-Wire sensor
To replace a sensor
•
Disconnect old sensor
•
Press ESC to enter the Main menu
•
Press Down until “Setup”
appears in the display
•
Press SEL to enter setup menu
•
“1W Sensor Setup” appears in the display
•
Press OK
•
select the sensor number in the list, it will say
“Sensor missing”
.
•
Connect new sensor and press SEL,
•
“
Tx
NEW=xxxxxx OK” is showed in the display
•
Confirm with OK
, “S
-
RID Saved” appears for 2 seconds
•
Temperature reading and ID is appearing in the display “T
X
=XX.X ID=xxxxxx”
•
Press ESC 4 times to go back to the main menu.
3.7.4
Clear all 1-Wire sensors
To clear all configured 1-Wire sensors
•
Press ESC to enter the Main menu
•
Press Down until “Setup”
appears in the display
•
Press SEL to enter setup menu
•
Press down until “Clear 1W Sensors”
is showed in the display
•
Press OK
•
“Clearing..” appears and then your back in the s
etup menu
This will clear all sensor including preconfigured sensors. You can now connect the sensors again,
see section 3.7.2.
3.7.5
Trouble shoot 1-Wire sensors
•
“
No
tempsensors or conn. Wrong. OK?”
is showed while configuring sensors.
Check wiring and make sure all sensors are connected properly (Data, GND). If the wires
from one (1) sensor is mixed up the whole 1-Wire bus stops.
•
“No new s
-
r found”
is showed when trying to connect/configure sensor.
Check wiring and make sure sensor is not already connected/configured on a different
position.