                  NPM User Manual 

15. Water: connect water sensor 

16. Smoke: connect smoke sensor 

17. T/H1, T/H2, T/H3: connect temperature/humidity sensor 

18. Port2

RS485

 

spare port 

20. Overload protection 

21. Cable input   

. Mounting Method 

Horizontal installation. 

. Hardware Introduction

 

1. Power on & Self-check 

The buzzer makes a sound when NPM is connected with AC power source, LED screen lightening and 

sequentially display 

8.8.8.  8.8.8.

 (it means digitron is normal, any different display means fault), software 

version number (for example

 U0.0    1.01

), baud rate (for example

9  600

), NPM default address (For example 

ABC  DEF

), NPM series (for example

310  1-d

), socket quantity(for example

 OU7  08

), finally display the 

value of which OUTLET No.1 pointing to (for example

 A1  0.0

), and RUN indicator flashes. M/S indicator on 

means this NPM is master while off means slave NPM. 

2. Current, voltage, temperature & humidity Monitoring   

OUTLET No.1 and OUTLET No.2 are together used to monitor the relative outlet value (OUTLET No.2 has the 

function of plus 8 port or minus 8 port). 

3. Water logging & Smoke Monitoring 

3.1 When the water logging sensor monitoring the water, NPM LED screen displays       and the buzzer 

alarms at the same time. 

3.2 When the smoke sensor monitoring the smoke, NPM LED screen displays             

and the buzzer alarms at 

the same time. 

4. Outlet Fault Monitoring 

When one outlet breaks down (For example: A1), the NPM LED screen will display relative fault (for example:

 

A1  Err

, and the buzzer alarms at the same time. 

5. Individual current, total current, voltage, temperature & humidity over the Limit monitoring 

5.1 When individual load current, total load current, voltage, temperature & humidity value are lower than the 

Min., the NPM screen displays as 

A.1

 

(that means the load current of outlet No. 1 is lower than the Min. value) 

5.2 When individual load current, total load current, voltage, temperature & humidity value are higher than the 

 

5

Содержание NPM 3100

Страница 1: ...NPM User Manual 1 NPM 3100 Network Power Manager User Manual ...

Страница 2: ...g Smoke Monitoring 5 4 Outlet Fault Monitoring 5 5 Individual Current Total Current Temperature Humidity Over Limit Monitoring 5 6 Self checking Parameter Monitoring 5 7 Stopping Alarm Monitoring 5 8 Master Slave NPM Configuration 6 9 Daisy chain Connection Method 6 10 Radialized Connection Method 6 11 Software Upgrade in Hardware 7 Ⅶ Software Introduction 8 1 Software Overview 8 2 Access Method 8...

Страница 3: ...ned alarming the limit of total load current individual load current for NPM B and D series and temperature humidity 5 System default alarming system alarming when total load current individual load current beyond the limit for NPM B and D series individual outlet breaks down smoke appears water logging or door opening 6 Alarming methods problem information show on LED screen and NPM buzzer alarms...

Страница 4: ...scription 4 1 19 outlets 2 Port1 The software upgrade port of hardware 3 LINK when daisy chain NPM connect with the SER port of the next NPM 4 SER for daisy chain 5 NET RI 45 port to connect PC Hub router or switch 6 No 2 select outlet 7 RESET set master or slave NPM and reset NPM press 30 seconds 8 Mounting bracket 9 10 Display NPM address and other parameters 11 RUN operation indicator 12 M S Ma...

Страница 5: ...t voltage temperature humidity Monitoring OUTLET No 1 and OUTLET No 2 are together used to monitor the relative outlet value OUTLET No 2 has the function of plus 8 port or minus 8 port 3 Water logging Smoke Monitoring 3 1 When the water logging sensor monitoring the water NPM LED screen displays and the buzzer alarms at the same time 3 2 When the smoke sensor monitoring the smoke NPM LED screen di...

Страница 6: ... 5 8 seconds the indicator of M S off indicates the NPM is the slave NPM Account the time please refer to the RUN indicator T 2S 9 Daisy chain Connection Method 9 1 Each NPM owns the sole default address which is different from others The address has been locked before leaving factory and can not be changed 9 2 Set one NPM as master and the others as slaves One master can daisy chain 9pcs NPM slav...

Страница 7: ...VER 10 4 Use the end of another network wire connects to another in out port of the HUB the other end connects to the SER port of the slave Each in out port of HUB connects to the SER port of one slave NPM can link 9pcs slave at most 10 5 Through IE to access Details please refers to the software introduction 11 Software Upgrade in Hardware 11 1 Clever will provide the file of software upgrade ple...

Страница 8: ...ely control and management er SNMP SSH and Telnet stem will automatically log out if the user please check the connectio 11 11 Power off the NPM 11 12 Power on the NPM L then it can work normally Ⅶ Software Introdu 1 Software overview This software is a technology that employs the total embedded system solution It is based on the monitoring technology of SNMP standard protocols encryption of SSH d...

Страница 9: ...s over the limiting value to alarm d Output Status sho means on means off means problem ice and its default status was NONE the user can switch on off single outlet multiple outlet consumption can be read if the device equipped with power consumption meter If not it will display ad if e equipped If not it will display Not found The digit in red will flash if the sensors alarm Temperature Humidity ...

Страница 10: ...tails as c Smoke alarm displays the connection of smoke sensor Not found means no smoke alarm is connected The word CLOSE o alarm happens d Water logging displays the status of water sensor Not found means no water sensors is connected The wor YES or NO can be rea 3 Device Configuration Configu below a NPM Address No each device has a unique series number the user ca device if the displayed figure...

Страница 11: ...the administrato voice or e mail wh a Voice alarm Select the voice document from the PC through the interface prompt save it after testin The interface displays the path of the voice document and prompt of setting success The PC will alarm through the voice set by user voice path and only one voice path can be saved Note The voice a b E mail alarm Select Enable e mail alarm POP3 address receive e ...

Страница 12: ...ext to view the daily record d Select WEB or EXCEL to leading out the daily record information e clear all 9 System a View the latest software versi and total system operation time b Click reset system settings to restore factory settings e g Device Configuration Al SNMP U 10 Web Configure HTTP user can enable or disable the HTTP port details as below Set and save the HTTP port according to the ne...

Страница 13: ...f SNMP records the information of SNMP f SNMP server position record the server position inform Note the SN 13 Update To upgrade the software the image bin file packet from supplier is requir the updating process according to the prompt message details a Connecting device and the PC directly by network cable b Click Browse c Click Update d Return to prompt information automati update document subm...

Страница 14: ...sponding SNMP management software after completing the SNMP start setting set up the configuration according to the software menu provided by SNMP software company leading in MIB file on the SNMP management platform user can monitor and manage the device status information and alarm Trap information after status are as detailed in figure 2 1 figure 2 2 and sensor can be read through the table form...

Страница 15: ...tion automatically the time information of alarm device name and the alarm type will be included in the 2009 11 07 56 device ow 16 0 nversation and power management SSH client agent lots of free shared software like PUTTY are mmand line like STATUS ON OFF REBOOT ADD REMOVE RESET RESTART QUIT TRAP information Overview of the TRAP information as below Minor 11 17 thresholdAlert 1 unitName 0 DisplayS...

Страница 16: ...t and the current threshold SENSORS midity door View the sensor status e g the current status of the temperature hu water smoke sensors and the threshold of temperature humidity For instance STATUS ABCDEF 5 View the status of output 5 of the NPM whose series number is ABCEDF e g of switch on off load current and threshold of current SS the series number of connected device control the status of sw...

Страница 17: ...off O escription PTION D ALL Switch off all the output of the device NO This option only require output number switch off only one outlet at a time For instance 4 REBOOT REBOOT command line can restart the individual or total outputs Command line input format REBOOT ADDRESS OPTION ADDR number No to be controlled according to the options as detaile O Description PTION ALL Restart all the output of ...

Страница 18: ...sender s address ONINTERVAL View the power on interval of this ADDRESS ADDRESS OUTPUTS ADDRESS View the output name and address information of this ADDRESS ALL g and time of power on off of all output of this View time settin ADDRESS TIMING ADDRESS NO NO means outlet number input one outlet View time setting and time of power on off of this individual output of this ADDRESS number at a time For in...

Страница 19: ...ption ENABLE Set the HTTP enable DISABLE Set the HTTP disable PORT Set the HTTP port For instance SET TELNET ENABLE enable TELNET function LNET setting will be valid after reboot OPTION OPTION as detailed in fig Figure 3 6 d the description table of SSH OPTION SH enable setting will be valid after reboot OPTION Description ENABLE Set the HTTP enable DISABLE Set the HTTP disable PORT Set the HTTP p...

Страница 20: ... The destinati n to be sent on 2 of Trap informatio CONTACT SNMP system contact SYSNAME SNMP system name LOCATION SNMP system address For instance SET SNMP ENABLE set the SNMP enable Note NULL can clear the configuration SNMP setting will be valid after reboot P OPTION OPTION as detailed in fig Figure 3 6 f the description table TION F MAIL Command line input format SET SNM ure in 3 6 f of MAIL OP...

Страница 21: ...ure sensor 1 L Set the lowest value of humidity sensor 1 HUM1 H Set the highest value of humidity sensor 1 L Set the lowest value of temperature sensor 2 TEM2 S H et the highest value of temperature sensor 2 L Set the lowest value of humidity sensor 2 HUM2 H Set the highest value of humidity sensor 2 L Set the lowest value of temperature sensor 3 TEM3 S H et the highest value of temperature sensor...

Страница 22: ... week on with 2 digits 24 hour clock re Monday Tuesday Wednesday Thursday Friday Saturday Sunday whose series number is ABCDEF to be 0 Note Temperature rating 40 Humidity rating 0 100 Current rating H TIMING SEG TIMING adjust the device time set the time of device power on off Command line input format SEG TIMING ADDRES ADDRESS the series number of connec n Figure 3 6 h OPTION Description CHECK Ad...

Страница 23: ...he device name output name and serial number Command line input format SET DEVIC figure 3 6 j e of DEVICE PTION Description NAME Change the device name ADDRESS Change the device serial number NO Change the name of each outlet Note the length of device name can not exceed 20 bytes e required if there is a blank in the name DD DEVICE 2 ABCDEF the series number of new added device 2 is ABCDEF REMOVE ...

Страница 24: ...nd user management Note it will be va 10 RESTART RESTART command line can be used to restart the system the SSH interface will be closed restart syst 11 QUIT QUIT to close the SSH system 2 4 TELNET command line console access The application of Telnet provides the user with the ability of remotely login and controlling conveniently start the conversation by inputting the user name an telnet progra...

Страница 25: ...s num B The name can not be repeat when nam IV Restore the network configuration Restore the network configuration of hardware restore IP address sub net mask default gateway DNS setting SSH Telnet HTTP to factory settings for th of restoring by network are as below A Connected the device and PC direc NO 1 knob on the front panel to U B Set up the device as Mater the Slaves can not be restored C P...

Страница 26: ...NPM User Manual 26 4 Ensure all the information filled in frame is accurate ...