Section 3 — Commissioning
Part No. 750-375
3-5
After confirming a new IP address for the PLC, this address must be
entered into the PanelView configuration settings.
1. Go to <PanelView Configuration> and from the PV Config main
screen select <Terminal Settings>.
2. From the Terminal Settings menu choose Networks and
Communications, then select RSLinx Enterprise Communications
and press the Enter arrow.
3. Highlight the Ethernet IP address for the PLC and press <Edit
Device>.
4. Press <Device Address> and enter the correct PLC IP address for
this system.
5. Press Enter, then <OK>.
Boiler/ADAC Ethernet Configuration
The individual boiler (see
SECTION A
above) and ADAC IP paths
need to be configured in the Master Panel.
From the System Configuration screen, go to <Boiler/ADAC Ethernet
Config>.