![CleaverBrooks CFC ClearFire Скачать руководство пользователя страница 50](http://html.mh-extra.com/html/cleaverbrooks/cfc-clearfire/cfc-clearfire_user-manual_2622067050.webp)
Model CFC
ClearFire Commercial Boilers
50
Rev. 05-2012
Boiler Room
Combustion and
Ventilation Air
The boiler(s) must be supplied with adequate quantities of uncontaminated air to
support proper combustion and equipment ventilation. Air shall be free of chlorides,
halogens, fluorocarbons, construction dust or other contaminants that are
detrimental to the burner/boiler. If these contaminants are present, we recommend
the use of direct vent combustion provided the outside air source is
uncontaminated.
Combustion air can be supplied by means of conventional venting, where
combustion air is drawn from the area immediately surrounding the boiler (boiler
room must be positive pressure), or with direct vent (direct vent combustion) where
air is drawn directly from the outside. All installations must comply with local Codes
and with NFPA 54 (the National Fuel Gas Code - NFGC) for the U.S. and for
Canada, CAN/CGA B 149.1 and B 149.2.
Note: A boiler room exhaust fan is not recommended as this type of device can cause a negative
pressure in the boiler room if using a conventional air intake.
In accordance with NFPA54, the required volume of indoor air shall be determined
in accordance with the "Standard Method" or "Known Air Infiltration Rate Method.
Where the air infiltration rate is known to be less than 0.40 Air Changes per Hour,
the Known Air Infiltration Rate Method shall be used. (See Section 8.3 in the
NFPA54 Handbook for additional information.)
Combustion Air
Supply - Unconfined
Spaces (For U.S.
Installations Only)
A.
All Air From Inside the Building
- If additional combustion air is drawn from
inside the building (the mechanical equipment room does not receive air
from outside via louvers or vent openings and the boiler is not equipped with
direct vent combustion) and the boiler is located in a unconfined space, use
the following guidelines:
1. The mechanical equipment room must be provided with two permanent
openings linked directly with additional room (s) of sufficient volume so
that the combined volume of all spaces meet the criteria for an
unconfined space. Note: An "unconfined space" is defined as a space
whose volume is more than 50 cubic feet per 1,000 Btu per hour of
aggregate input rating of all appliances installed in that space.
2. Each opening must have a minimum free area of one square inch per
1,000 Btu per hour of the total input rating of all gas utilizing equipment
in the mechanical room.
3. One opening must terminate within twelve inches of the top, and one
opening must terminate within twelve inches of the bottom of the room.
4. Refer to the NFGC, Section 8.3 for additional information.
Содержание CFC ClearFire
Страница 9: ...Model CFC ClearFire Commercial Boilers 9 Rev 05 2012 Figure B5 6 Model CFC Dimensional Views I ...
Страница 64: ...Model CFC ClearFire Commercial Boilers 64 Rev 05 2012 Figure B5 54 Electrical Connections CFC 500 2500 ...
Страница 65: ...Model CFC ClearFire Commercial Boilers 65 Rev 05 2012 Figure B5 55 Electrical Connections CFC 3300 ...
Страница 66: ...Model CFC ClearFire Commercial Boilers 66 Rev 05 2012 Figure B5 56 CFC Rear Connections ...
Страница 70: ...Model CFC ClearFire Commercial Boilers 70 Rev 05 2012 ...