Model CFC
ClearFire Commercial Boilers
20
Rev. 05-2012
Noise Level
The Model CFC is extremely quiet at all operating levels, does not require any sound
level modifications to provide ultra low noise levels, and is virtually vibration free.
Thus, it is very suitable in applications that demand low noise levels.
Table B5-11 shows the noise levels of the Clearfire at various firing rates.
Table B5-11. Noise Level (dBA) measured 3 feet in front of boiler
ENGINEERING DATA
Boiler Information
The Model CFC boiler is designed for service in any closed hydronic system and can
be used to augment any hot water system. It can be put into operation as a single
stand-alone unit with 5:1 turndown or in multiple units for larger turndown and
capacity.
Clearfire boilers may be utilized in water heating systems with temperatures from
40
F (4.4
C) to 195
F (90.5
C); ideal for ground water source heat pump
applications, etc. Because the Clearfire is a full condensing boiler, low water
temperature (below the dewpoint) restrictions do not apply. In fact, the lower the
return the better the fuel savings.
Variable temperature differentials can be designed to make use of changing outdoor
conditions and thus, the Clearfire is not restricted to a nominal 20
F (10 C)
differential. The boiler is designed to withstand thermal stresses with supply and
return temperature differences up to 100
F (55
C), without the use of a boiler-
circulating pump, blend pump or minimum water flow.
Note: The Clearfire does not require a minimum flow or continuous flow through it during operation.
However, the load imposed on the boiler must be considered when sizing the system flow so that
the flow does not exceed the capacity of the boiler or the demand.
Flow Rates and
Pressure Drops
To maintain rated capacity of the boiler, recommended flow rates should not be
exceeded as the flow will remove the heat beyond the capacity of the boiler. Table
B5-12
through
Table B5-13 can be used to determine the full boiler output relative
to system temperature drop and the maximum recommended system pump flow.
Knowing the flow rate, the pressure drop through the boiler can be found in Figure
B5-14
through Figure B5-19.
System Operating
Parameters
To prevent water flashing to steam within the boiler or system, hot water boilers
must operate with proper over-pressure. System over-pressure requirements are
shown in Table B5-14.
Note: The ASME Code Section IV limits the maximum setting of the excess temperature control to
210
F (98.9
C) for boilers constructed with stainless steel. This is to ensure that water
temperature will not reach the boiling point (steaming) and therefore, so as not to exceed the
maximum limit of this control and in compliance with the Code, the operating limit of 195
F
20% Firing
60% Firing
100% Firing
CFC 500
39
48
60
CFC 750
41
51
62
CFC 1000
43
57
66
CFC 1500
40
50
64
CFC 1800
45
56
66
CFC 2500
45
57
68
CFC 3300
63
73
78
Содержание CFC ClearFire
Страница 9: ...Model CFC ClearFire Commercial Boilers 9 Rev 05 2012 Figure B5 6 Model CFC Dimensional Views I ...
Страница 64: ...Model CFC ClearFire Commercial Boilers 64 Rev 05 2012 Figure B5 54 Electrical Connections CFC 500 2500 ...
Страница 65: ...Model CFC ClearFire Commercial Boilers 65 Rev 05 2012 Figure B5 55 Electrical Connections CFC 3300 ...
Страница 66: ...Model CFC ClearFire Commercial Boilers 66 Rev 05 2012 Figure B5 56 CFC Rear Connections ...
Страница 70: ...Model CFC ClearFire Commercial Boilers 70 Rev 05 2012 ...