Table B5-4. Altitude Correction for Input Capacity at Various Altitude Levels
Natural Gas
700' ASL
2000'
4000'
6000'
8000'
10000'
CFC 3300
3300 kBTU/h
3300
3300
3300
3057
2930
CFC 2500
2500
2418
2245
2083
1930
1850
CFC 1800
1800
1800
1800
1666
1544
1480
CFC 1500
1500
1500
1500
1415
1311
1257
CFC 1000
1000
1000
1000
943
874
838
CFC 750
750
750
750
707
655
628
CFC 500
500
500
490
454
421
404
Ratings assume 35% excess air, 80F combustion air.
Blower speed adjustments should be made to match performance and local conditions accordingly.
For minimum gas supply pressures see Table B5-24. Altitude corrections for supply pressure should be made per Table B5-25
.
Natural gas heating value of 1000 BTU/SCF assumed.
LP Gas
700' ASL
2000'
4000'
6000'
8000'
10000'
CFC 3300
3300 kBTU/h
3300
3300
3300
3057
2930
CFC 2500
2500
2500
2339
2169
2010
1927
CFC 1800
1800
1800
1800
1704
1579
1514
CFC 1500
1500
1500
1500
1500
1390
1332
CFC 1000
1000
1000
1000
1000
926
888
CFC 750
750
750
750
750
695
666
CFC 500
500
500
500
481
445
427
Ratings assume 40% excess air, 80F combustion air.
Blower speed adjustments should be made to match performance and local conditions accordingly.
For minimum gas supply pressures see Table B5-24. Altitude corrections for supply pressure should be made per Table B5-25
.
LP (propane) gas heating value of 2500 BTU/SCF assumed.
Содержание CFC ClearFire
Страница 9: ...Model CFC ClearFire Commercial Boilers 9 Rev 05 2012 Figure B5 6 Model CFC Dimensional Views I ...
Страница 64: ...Model CFC ClearFire Commercial Boilers 64 Rev 05 2012 Figure B5 54 Electrical Connections CFC 500 2500 ...
Страница 65: ...Model CFC ClearFire Commercial Boilers 65 Rev 05 2012 Figure B5 55 Electrical Connections CFC 3300 ...
Страница 66: ...Model CFC ClearFire Commercial Boilers 66 Rev 05 2012 Figure B5 56 CFC Rear Connections ...
Страница 70: ...Model CFC ClearFire Commercial Boilers 70 Rev 05 2012 ...