background image

FILTRATION

FILTRATION

WWW.CLEANCOMFORT.COM

11

TROUBLESHOOTING

IO-AE14-5

1.  Remove both cells from the air cleaner cabinet.  

Replace the cabinet door.

2.  Toggle the air cleaner’s orange power switch 

ON

,  

and turn the HVAC fan 

ON

.

3.  If the green performance indicator light is still 

OFF

check the power board for an arc to ground at HV1  

or HV2. Refer to Troubleshooting section .

4.  If there is a good arc and the performance indicator 

light is still 

OFF

, then replace the light. Refer to Service 

section A “Replacing a Performance Light”. 

If the performance indicator light comes 

ON

, check  

the cells for a fault. Refer to Troubleshooting sections  

, and .

5.  If there is no arc, test the output voltage of the  

transformer. Refer to Troubleshooting section .

If there is transformer output, replace the power 

board. Refer to Service section B) “Replacing a  

Power Board”If there is no transformer output,  

check for output of the APS. Refer to Troubleshooting 

section .

•  If there is output from the APS, replace the trans-

former (refer to Service section C) “Replacing the  

24 V Transformer”) and retest the power board for 

an arc. Refer to Troubleshooting section .

•  If there is no output from the APS, jumper terminals  

3 & 4 on the APS and retest the output. If there is  

APS output with the jumper installed, replace the 

APS. Refer to Service Section D) “Replacing an Air 

Proving Switch (APS).

6.  If there is still no output from the APS, check the output 

voltage from the power switch.

7. If there is no voltage from the power switch, test the input 

to the switch. If there is input, replace the power switch. 

8.  If there is no input to the switch, check the interlock 

switch and the supply voltage. 

Troubleshooting

The air cleaner, when operating normally with the fan 

running, should have both the orange power switch light 

and the green performance indicator light 

ON

. If the fan is 

running and the lights are not on, follow instructions below 

for probable causes and remedies.
Quick Check (Orange Power Switch Light 

ON

, Green 

Performance Indicator Light 

OFF

)

Detailed Troubleshooting

 Testing For High Voltage at Power Board

With the collecting cells out of the unit, the door on the unit 

and the system fan on high speed, turn the air cleane

r ON

With a long shafted screwdriver with a plastic handle, short 

between the grounded side of the power box and the HV1 

terminal of the power board. If you draw a good spark, 

there is high voltage from the power board. 

② Measuring High Voltage at Power Board

A high voltage meter capable of measuring up to 10,000 

VDC is required to test the voltage. 

i

 

CAUTION! 

 

 

For most troubleshooting, the cells should be removed 

 

from the air cleaner. A short in one of the cells will cause 

 

the power board to shut down and the performance light 

 

will stay 

OFF

. Unless otherwise directed, remove the cells 

 

from the unit when testing. 

i

 

WARNING! 

 

 

When performing LIVE tests in the power box, 

NEVER  

 

touch any parts other than what is mentioned in the tests. 

 

Components carry dangerous voltages and extreme care 

 

must be taken. 

1.  The air cleaner should be 

ON

 with the cells installed, 

the door closed and the system fan running.  

The air cleaner should be on at least 5 minutes  

to allow voltage to stabilize. The cells and ionizing 

wires must be clean.

2.  Remove the cover from power box.
3.  Connect the ground of the high voltage meter to an 

unpainted surface in the power box.

4.  Check terminals HV1 and HV2 on the power board to 

determine if voltage is present. See Table 3 for values

If no voltage is present, remove both cells from the  

air cleaner and replace door. Recheck the voltage at  

HV1 and HV2  

 

If voltage is present, the problem is with one of the  

cells or the wiring to the copper contacts. 

   

With a flashlight, look into the cabinet to check  

condition of the copper contacts. 

 

If the contacts are not bent, replace one cell and  

retest voltage. If cell is OK, test the other cell. If the  

problem is with a cell, see Troubleshooting sections  

, and 

 

If there is no voltage with both cells removed, 

check the power board, APS and transformer to 

make sure that they are functioning correctly.

Содержание AE14-1620-51

Страница 1: ...TANT READ AND SAVE THESE INSTRUCTIONS THIS GUIDE TO BE LEFT WITH EQUIPMENT OWNER i HIGH EFFICIENCY ELECTRONIC AIR CLEANER Installation Operation Manual MODELS AE14 1620 51 AE14 1625 51 AE14 2020 51 AE14 2025 51 120 VAC AE14 1620 52 AE14 1625 52 AE14 2020 52 AE14 2025 52 240 VAC ...

Страница 2: ...eplacing a Performance Light 16 Replacing a Power Board 16 Replacing the 24 V Transformer 16 Replacing an Air Proving Switch APS 17 Removing Power Box 17 Replacing a Tungsten Ionizing Wire 17 PARTS LIST 18 LIMITED WARRANTY 20 Proprietary Notice This document and the information disclosed herein are proprietary data of Daikin North America LLC Neither this document nor the information contained her...

Страница 3: ... inch Features and Benefits Two aluminum mesh prefilters help prevent lint and large particles from entering the collecting cells Features a permanent washable filter system Heavy gauge aluminum collecting cells are durable and easy to maintain Washing the collecting cells takes only 15 minutes Activated carbon VOC filters help remove unpleasant odors such as those from cooking smoking or other ho...

Страница 4: ...particles from entering the collecting cells Carbon VOC Filters Remove odors Maximum of 3 carbon VOC filters can be used at the same time 120V MODELS AE14 1620 51 AE14 1625 51 AE14 2020 51 AE14 2025 51 240V MODELS AE14 1620 52 AE14 1625 52 AE14 2020 52 AE14 2025 52 House Size Area typical up to 2400 ft up to 223 m up to 3000 ft up to 279 m up to 3000 ft up to 279 m up to 4000 ft up to 372 m Airflo...

Страница 5: ...eaner and remove prefilters collecting cells and power box for maintenance Note Once the air cleaner has been installed do not allow the placement of any device such as a new hot water heater water softener gas pipe or electrical cable to be put 24 in 61 cm in front of or within 6 in 15 cm from top of air cleaner This distance is needed to allow access for the removal of filters and air cleaner pa...

Страница 6: ...attach cabinet to ductwork or equipment If the adjoining ductwork is flanged install the screws so that the screw heads are inside the cabinet This will help prevent damage to prefilter and carbon VOC filters during removal for cleaning Never put screws or rivets into the removable power box 4 Transitions If the air duct does not fit the air cleaner opening a gradual transition is recommended to r...

Страница 7: ...o power this air cleaner with the fan operating in all conditions The air cleaner uses approximately 30 Watts when operating Some systems do not power the EAC contacts on the system module on low speed System Check Perform the following system check before operation 1 Replace prefilters collecting cells and carbon VOC filters Close the access door 2 Turn air cleaner power switch ON Ensure system f...

Страница 8: ...stream side of the air cleaner and the activated carbon VOC filters are on the downstream side The handles on the collector cells are facing the front of the air cleaner cabinet The collector cells and aluminum prefilters are clean and dry All joints in sheet metal between the air cleaner and the heating and cooling system are sealed Previously installed furnace filter has been removed if present ...

Страница 9: ...DAX Detergent and dunk cells up and down until water is dirty 3 If dirt remains on the cell plates let the cells soak in a solution of DAX Detergent and water for 30 minutes 4 When the collector cells are clean drain the tub and rinse cells thoroughly with hot water maximum 120 F 49 C 5 Remove accumulated particulate from the ionizing wires with an old toothbrush Slide the brush bristles over the ...

Страница 10: ...le 2 Replacement carbon VOC filters are available in the same size and configuration as the original unit They can be purchased from your Clean Comfort authorized service technician 1 Turn air cleaner power switch OFF 2 Turn OFF system fan 3 Open access door 4 Remove collecting cells from air cleaner 5 Remove the used carbon VOC filters from air cleaner 6 Put new carbon VOC filters into air cleane...

Страница 11: ...s Quick Check Orange Power Switch Light ON Green Performance Indicator Light OFF Detailed Troubleshooting Testing For High Voltage at Power Board With the collecting cells out of the unit the door on the unit and the system fan on high speed turn the air cleaner ON With a long shafted screwdriver with a plastic handle short between the grounded side of the power box and the HV1 terminal of the pow...

Страница 12: ... the collecting cells turn the unit ON without the fan on The power board should come on immediately and then turn OFF in 20 30 seconds as the sensor heats up To check sensor blow directly on it lightly This should activate the power board within 10 seconds Service the sensor carefully The sensor leads are live If the APS does not turn the power board and performance indicator on by pass the APS b...

Страница 13: ... on high speed 3 Turn the air cleaner ON and press the safety interlock switch lever 4 Place a plastic handled screwdriver into the direction arrow slot Do not apply excessive force 5 If there is a good snap then there is high voltage at the cell Testing Cell for Bad Contacts 1 Open access door to air cleaner 2 The cells must be in the air cleaner for this test and the system fan should be on high...

Страница 14: ... indicator light Determine whether high voltage is present by testing power board If voltage is present replace performance indicator light Defective power board Adjust high voltage potentiometer on power board counter clockwise If high voltage is not present replace power board Air Proving Switch APS sensor is burnt out Remove power box lid and blow lightly for 10 seconds on APS sensor at bottom ...

Страница 15: ...ntacts with needle nose pliers or remove power box and replace contacts Cells not collecting dirt power light and performance indicator light ON Arrow on cells not pointing towards fan blower Reposition cell handle and place cell in properly System fan is on Automatic setting air cleaner not on continuously Use Fan On system fan setting for continuous fan operation Not enough voltage on collecting...

Страница 16: ...under the power board 7 Reconnect wiring to LED HV1 HV2 and 24 V terminals on the new power board 8 Return power to air cleaner Test power board 9 Replace power box cover C Replacing the 24 V Transformer Before replacing the transformer check the resistance across the power board s 24 V input terminals without the transformer connected Resistance should read above 20K ohms with an analog meter and...

Страница 17: ...he wires so the system can still be operated 4 Remove the two nuts holding the power box to the cabinet 5 Slide the power box forward then up to remove it from the cabinet 6 If you are removing the power box for any length of time tape a cover over the top opening to prevent air from entering into the system F Replacing a Tungsten Ionizing Wire Replacement wires are cut to the correct length and h...

Страница 18: ... D1 053E D1 053E D1 053E D1 053E 6 Power Board 120VAC models D1 055D D1 055D D2 055D D2 055D Power Board 220VAC models D1 055E D1 055E D2 055E D2 055E 7 Fibreboard with 4 Copper Contacts D0 0521 D1 0521 D2 0521 D8 0521 8 Copper Contact R1 9925 R1 9925 R1 9925 R1 9925 9 Cord Assembly Optional R1 062D R1 062D R1 062D R1 062D 10 Cover for Power Box D0 0509 D1 0509 D0 0509 D1 0509 11 Power Box Complet...

Страница 19: ...FILTRATION WWW CLEANCOMFORT COM 19 IO AE14 5 NOTES ...

Страница 20: ...DE HEREIN MAY NOT BE ALTERED ENLARGED OR CHANGED BY ANY DISTRIBUTOR DEALER OR OTHER PERSON WHATSOEVER CONSEQUENTIAL OR INCIDENTAL DAMAGES FOR THE BREACH OF ANY WARRANTY WHETHER EXPRESS OR IMPLIED FOR ANY OTHER CONTRACT BREACH OR FOR NEGLIGENCE OR OTHER TORT INCLUDING BUT NOT LIMITED TO LOSSES OF PROPERTY ARISING OUT OF THE FAILURE OF THIS EQUIPMENT TO OPERATE FOR ANY REASON WHATSOEVER ARE EXCLUDED...

Отзывы: