background image

FILTRATION

FILTRATION

WWW.CLEANCOMFORT.COM

6

IO-AE14-5

INSTALLATION

Figure 5: 

Air Cleaner

Installation Location

Allow 24 in. (60 cm) clearance for maintaining air cleaner 

Allow 6 in. (15 cm) clearance for power box removal.

Installation Location with Humidifier

A humidifier should be installed in the furnace warm 

air duct. However, it may be installed in the return duct 

without causing problems to the air cleaner. Care must 

be taken to ensure that the humidifier does not leak, as 

this may cause arcing and a mineral deposit to build up 

on the collecting cells.
An atomizing type humidifier should be installed 

downstream from the air cleaner. If the atomizing type 

humidifier is installed upstream, high humidity, salts and 

minerals may decrease the efficiency of the collecting 

cells and cause service problems.
If the atomizing type humidifier must be installed 

upstream, the following precautions should be taken:

1.  Atomizing type humidifier must be installed as far 

from the air cleaner as possible.

2.  Collecting cells must be washed frequently to 

prevent a mineral deposit build-up.

Installation Location with Air Conditioner

Whenever possible, the air cleaner should be installed 

upstream of the cooling coil. This location will clean the 

air before it reaches the evaporator coil.

Installation Steps

1. 

Remove existing equipment filter (if present) and 

clean blower compartment:

 Thoroughly clean the 

blower compartment, since your air cleaner can not 

remove accumulated dirt from the blower chamber 

and distribution ducts.

2. 

Open air cleaner access door. Slide filters and 

collecting cells out of cabinet.

3.  Installing the cabinet: Holes are provided to attach 

cabinet to ductwork or equipment. If the adjoining 

ductwork is flanged, install the screws so that the 

screw heads are inside the cabinet. This will help 

prevent damage to prefilter and carbon VOC filters 

during removal for cleaning. Never put screws or 

rivets into the removable power box.

4. 

Transitions: If the air duct does not fit the air cleaner 

opening, a gradual transition is recommended to 

reduce air turbulence through the air cleaner and 

ensure its efficient operation. A maximum of 20° of 

expansion, or approximately 4 inches per running foot 

(10 cm per 30 cm ), is recommended for each side of 

the transition fitting. 

 

Do not reduce ductwork size to fit a smaller  

air cleaner. This will increase the velocity of  

airflow and may decrease cleaning efficiency.

5. 

Turning vanes: If the air cleaner is installed adjacent 

to an elbow or angle fitting, field-installed turning 

vanes are recommended to improve air distribution 

across the collecting cells.

6. 

Seal the joints in the return air system: All joints 

between the air cleaner, the heating / cooling 

equipment and the return air duct should be sealed  

to prevent dust from entering the clean air stream.

7. 

Replace the prefilters in the track on the air entering 

side of the air cleaner. Place new carbon VOC filters 

into the air cleaner. Space filters evenly across the 

discharge opening of air cleaner. Never put more  

than 3 carbon VOC filters in the air cleaner, as this 

may cause a problem with airflow.  

 

The collecting cells are placed between the tracks, with 

the arrow on cell pointing towards the fan. The cell 

handle may need to be repositioned if the airflow is in 

a different direction than the left to right set up. The 

handle should face the door. Close access door.

i

 

WARNING! 

 

 

Electrical shock can cause injury or death. Be certain main 

 

line disconnect switch is 

OFF

 before wiring. 

Содержание AE14-1620-51

Страница 1: ...TANT READ AND SAVE THESE INSTRUCTIONS THIS GUIDE TO BE LEFT WITH EQUIPMENT OWNER i HIGH EFFICIENCY ELECTRONIC AIR CLEANER Installation Operation Manual MODELS AE14 1620 51 AE14 1625 51 AE14 2020 51 AE14 2025 51 120 VAC AE14 1620 52 AE14 1625 52 AE14 2020 52 AE14 2025 52 240 VAC ...

Страница 2: ...eplacing a Performance Light 16 Replacing a Power Board 16 Replacing the 24 V Transformer 16 Replacing an Air Proving Switch APS 17 Removing Power Box 17 Replacing a Tungsten Ionizing Wire 17 PARTS LIST 18 LIMITED WARRANTY 20 Proprietary Notice This document and the information disclosed herein are proprietary data of Daikin North America LLC Neither this document nor the information contained her...

Страница 3: ... inch Features and Benefits Two aluminum mesh prefilters help prevent lint and large particles from entering the collecting cells Features a permanent washable filter system Heavy gauge aluminum collecting cells are durable and easy to maintain Washing the collecting cells takes only 15 minutes Activated carbon VOC filters help remove unpleasant odors such as those from cooking smoking or other ho...

Страница 4: ...particles from entering the collecting cells Carbon VOC Filters Remove odors Maximum of 3 carbon VOC filters can be used at the same time 120V MODELS AE14 1620 51 AE14 1625 51 AE14 2020 51 AE14 2025 51 240V MODELS AE14 1620 52 AE14 1625 52 AE14 2020 52 AE14 2025 52 House Size Area typical up to 2400 ft up to 223 m up to 3000 ft up to 279 m up to 3000 ft up to 279 m up to 4000 ft up to 372 m Airflo...

Страница 5: ...eaner and remove prefilters collecting cells and power box for maintenance Note Once the air cleaner has been installed do not allow the placement of any device such as a new hot water heater water softener gas pipe or electrical cable to be put 24 in 61 cm in front of or within 6 in 15 cm from top of air cleaner This distance is needed to allow access for the removal of filters and air cleaner pa...

Страница 6: ...attach cabinet to ductwork or equipment If the adjoining ductwork is flanged install the screws so that the screw heads are inside the cabinet This will help prevent damage to prefilter and carbon VOC filters during removal for cleaning Never put screws or rivets into the removable power box 4 Transitions If the air duct does not fit the air cleaner opening a gradual transition is recommended to r...

Страница 7: ...o power this air cleaner with the fan operating in all conditions The air cleaner uses approximately 30 Watts when operating Some systems do not power the EAC contacts on the system module on low speed System Check Perform the following system check before operation 1 Replace prefilters collecting cells and carbon VOC filters Close the access door 2 Turn air cleaner power switch ON Ensure system f...

Страница 8: ...stream side of the air cleaner and the activated carbon VOC filters are on the downstream side The handles on the collector cells are facing the front of the air cleaner cabinet The collector cells and aluminum prefilters are clean and dry All joints in sheet metal between the air cleaner and the heating and cooling system are sealed Previously installed furnace filter has been removed if present ...

Страница 9: ...DAX Detergent and dunk cells up and down until water is dirty 3 If dirt remains on the cell plates let the cells soak in a solution of DAX Detergent and water for 30 minutes 4 When the collector cells are clean drain the tub and rinse cells thoroughly with hot water maximum 120 F 49 C 5 Remove accumulated particulate from the ionizing wires with an old toothbrush Slide the brush bristles over the ...

Страница 10: ...le 2 Replacement carbon VOC filters are available in the same size and configuration as the original unit They can be purchased from your Clean Comfort authorized service technician 1 Turn air cleaner power switch OFF 2 Turn OFF system fan 3 Open access door 4 Remove collecting cells from air cleaner 5 Remove the used carbon VOC filters from air cleaner 6 Put new carbon VOC filters into air cleane...

Страница 11: ...s Quick Check Orange Power Switch Light ON Green Performance Indicator Light OFF Detailed Troubleshooting Testing For High Voltage at Power Board With the collecting cells out of the unit the door on the unit and the system fan on high speed turn the air cleaner ON With a long shafted screwdriver with a plastic handle short between the grounded side of the power box and the HV1 terminal of the pow...

Страница 12: ... the collecting cells turn the unit ON without the fan on The power board should come on immediately and then turn OFF in 20 30 seconds as the sensor heats up To check sensor blow directly on it lightly This should activate the power board within 10 seconds Service the sensor carefully The sensor leads are live If the APS does not turn the power board and performance indicator on by pass the APS b...

Страница 13: ... on high speed 3 Turn the air cleaner ON and press the safety interlock switch lever 4 Place a plastic handled screwdriver into the direction arrow slot Do not apply excessive force 5 If there is a good snap then there is high voltage at the cell Testing Cell for Bad Contacts 1 Open access door to air cleaner 2 The cells must be in the air cleaner for this test and the system fan should be on high...

Страница 14: ... indicator light Determine whether high voltage is present by testing power board If voltage is present replace performance indicator light Defective power board Adjust high voltage potentiometer on power board counter clockwise If high voltage is not present replace power board Air Proving Switch APS sensor is burnt out Remove power box lid and blow lightly for 10 seconds on APS sensor at bottom ...

Страница 15: ...ntacts with needle nose pliers or remove power box and replace contacts Cells not collecting dirt power light and performance indicator light ON Arrow on cells not pointing towards fan blower Reposition cell handle and place cell in properly System fan is on Automatic setting air cleaner not on continuously Use Fan On system fan setting for continuous fan operation Not enough voltage on collecting...

Страница 16: ...under the power board 7 Reconnect wiring to LED HV1 HV2 and 24 V terminals on the new power board 8 Return power to air cleaner Test power board 9 Replace power box cover C Replacing the 24 V Transformer Before replacing the transformer check the resistance across the power board s 24 V input terminals without the transformer connected Resistance should read above 20K ohms with an analog meter and...

Страница 17: ...he wires so the system can still be operated 4 Remove the two nuts holding the power box to the cabinet 5 Slide the power box forward then up to remove it from the cabinet 6 If you are removing the power box for any length of time tape a cover over the top opening to prevent air from entering into the system F Replacing a Tungsten Ionizing Wire Replacement wires are cut to the correct length and h...

Страница 18: ... D1 053E D1 053E D1 053E D1 053E 6 Power Board 120VAC models D1 055D D1 055D D2 055D D2 055D Power Board 220VAC models D1 055E D1 055E D2 055E D2 055E 7 Fibreboard with 4 Copper Contacts D0 0521 D1 0521 D2 0521 D8 0521 8 Copper Contact R1 9925 R1 9925 R1 9925 R1 9925 9 Cord Assembly Optional R1 062D R1 062D R1 062D R1 062D 10 Cover for Power Box D0 0509 D1 0509 D0 0509 D1 0509 11 Power Box Complet...

Страница 19: ...FILTRATION WWW CLEANCOMFORT COM 19 IO AE14 5 NOTES ...

Страница 20: ...DE HEREIN MAY NOT BE ALTERED ENLARGED OR CHANGED BY ANY DISTRIBUTOR DEALER OR OTHER PERSON WHATSOEVER CONSEQUENTIAL OR INCIDENTAL DAMAGES FOR THE BREACH OF ANY WARRANTY WHETHER EXPRESS OR IMPLIED FOR ANY OTHER CONTRACT BREACH OR FOR NEGLIGENCE OR OTHER TORT INCLUDING BUT NOT LIMITED TO LOSSES OF PROPERTY ARISING OUT OF THE FAILURE OF THIS EQUIPMENT TO OPERATE FOR ANY REASON WHATSOEVER ARE EXCLUDED...

Отзывы: