FILTRATION
FILTRATION
WWW.CLEANCOMFORT.COM
5
IO-AE14-5
INSTALLATION
100% Airflow
No Carbon
VOC Filters
100% Airflow
With Carbon
VOC Filters
40% Airflow
No Carbon
VOC Filters
40% Airflow
With Carbon
VOC Filters
0.158
0.250
0.030
0.060
Static Pressure
The static pressure drop across the air cleaner will vary
with CFM and whether the carbon VOC filters have been
installed in the unit.
Table 2:
Pressure Drop (Inches w.c.)
Installation
Location:
The air cleaner must only be installed in the return air duct,
as close to the fan compartment as possible. This location
provides the most even airflow across the collecting cells
and helps the air cleaner to keep the system motor, blower,
and cooling coil clean. The installation can be vertical or
horizontal. When choosing a location, there must be ade-
quate room to wire the air cleaner and remove prefilters,
collecting cells, and power box for maintenance.
Note:
Once the air cleaner has been installed, do not allow
the placement of any device such as a new hot water heater,
water softener, gas pipe, or electrical cable
to be put 24 in. (61 cm) in front of or within
6 in. (15 cm) from top of air cleaner. This
distance is needed to allow access for the
removal of filters and air cleaner parts, which
are necessary for maintenance or servicing.
Dimensions — in (cm)
MODEL
A
B
C
D
E
F
G
H
AE14-1620-51
AE14-1620-52
19.8
(50.4)
15.9
(40.5)
23.2
(58.9)
13.1
(33.3)
20.7
(52.5)
1.3
(3.2)
23.7
(60.2)
21.2
(53.9)
AE14-1625-51
AE14-1625-52
19.8
(50.4)
15.9
(40.5)
26.1
(66.3)
13.6
(34.6)
24.1
(61.2)
1.0
(2.5)
26.6
(67.7)
25.8
(65.4)
AE14-2020-51
AE14-2020-52
24.7
(62.8)
20.8
(52.9)
21.2
(53.9)
18.0
(45.7)
18.7
(47.5)
1.3
(3.2)
21.7
(55.2)
21.2
(53.9)
AE14-2025-51
AE14-2025-52
24.7
(62.8)
20.8
(52.9)
25.8
(65.4)
18.0
(45.7)
23.3
(59.1)
1.3
(3.2)
26.3
(66.8)
25.8
(65.4)
Table 3:
Air Cleaner Dimensions
Figure 3:
Pressure Drop across Air Cleaner
2.80
Figure 4:
Dimensions