INSTALLATION CLEARANCES FOR CONSOLE MODELS
TEST NO.
HCMG/04/006
LARGE
CONSOLE
All clearances are
to combustibles.
150 mm
1090 mm
200 mm
350 mm
450 mm
1040 mm
Floor Protector: 6 mm CEMENT SHEET MIN.
STANDARD CORNER INSTALLATION
50 mm
50 mm
DIAGONAL CORNER INSTALLATION
TEST NO.
HCMG/04/020
MEDIUM
CONSOLE
All clearances are
to combustibles.
100 mm
920 mm
200 mm
300 mm
350 mm
940 mm
Floor Protector: 6 mm CEMENT SHEET MIN.
STANDARD CORNER INSTALLATION
50 mm
50 mm
DIAGONAL CORNER INSTALLATION
TEST NO.
RF/95/072
SMALL
CONSOLE
All clearances are
to combustibles.
100 mm
890 mm
200 mm
300 mm
350 mm
890 mm
Floor Protector: 6 mm CEMENT SHEET MIN.
STANDARD CORNER INSTALLATION
50 mm
50 mm
DIAGONAL CORNER INSTALLATION
NB: Small heater to have extra 450
mm stainless steel heat shield at
bottom of decromesh casing.
Clean Air Woodheaters tested by HRL Technology Pty Ltd to comply with Australian Standards when installed to
enclosed dimensions. The flue system used for testing was a Hawkwind Twistlock flue kit, manufactured by S V Metals.
This flue system has not been tested to joint AS/NZS 2918:2001. The flue height was 4.6 ± 0.3 m from the floor protector.
Local council building approval may be required in some states.