ENSURE AIR OUTLET LOUVRES ARE NEAREST 

TO THE DOOR APPERTURE.

 

3.1

 

Mounting

 

 

All  units  should  be  installed  horizontally  directly 

over the door opening. It is recommended that the 

air curtain is installed on the inside of the building, 

within  the  open  room  space  against  a  wall  or   

ceiling. 

 

 

Care  must  be  taken  to  allow  complete  free  air 

movement into the inlet grilles of the unit to ensure 

correct  working  operation  of  the  air  curtain.  The 

discharge opening should be as close to the top of 

the  door  as  possible  and  cover  the  entire  door 

width.

 

 

Units  can  be  mounted  adjacent  to  each  other  to 

cover  the  full  door  opening  across  wider           

entrances. 

 

 

 

The weight of the RAC0603 and RAC0604 is 8kg

 

 

The weight of the RAC1006 is 11.5kg

 

 

 

 

 

 

3.2

 

Electrical Installation

 

 

These units are suitable for connection to 230/240 

Volt 50 Hz single phase supply.

 

 

The  appliance  shall  be  connected  to  the  supply 

via  an  appropriate  switched  fused  double  pole 

isolator  having  a  contact  separation  of  greater 

than 3mm. Test for correct operation and refit the 

grille.

 

 

For  connection  to  the  mains  supply  it  will  be    

necessary to remove  the grille from the unit. It will 

be necessary to connect the mains supply and the 

lead  from  the  controls  prior  to  refitting  the  cover. 

Wire in accordance to wiring diagrams.

 

 

For  safety  reasons,  a  sound  earth  connection 

must always be made to the unit before it is put to 

use. The unit should be wired in accordance with 

IEE  Regulations  for  the  Electrical  Equipment  of 

Buildings.

 

 

 

 

 

 

 

 

 

3.3

 

Installation

 

 

It is the sole responsibility of the installer to ensure 

3. Installation Details

 

Fig.1 ceiling cutout for RAC0603 and RAC0604

 

Fig.2 ceiling cutout for RAC1006

 

Fig.3 Grille fixings detail

 

Содержание ScreenZone RAC0603

Страница 1: ...6 695195 Email technical consortepl com Web www consortepl com ScreenZone Recessed Warm Air Curtains Catalogue Numbers RAC0603 RAC0604 RAC1006 RAC0603RX RAC0604RX RAC1006RX Installation and Operating...

Страница 2: ...ests with the installer to en sure that all site safety procedures are ad hered to during installation Sole liability rests with the installer to en sure that protective safety wear such as hand eye e...

Страница 3: ...41001452 Iss 06 3 2 Dimensions 2 1 Air Curtain Dimensions...

Страница 4: ...rical Installation These units are suitable for connection to 230 240 Volt 50 Hz single phase supply The appliance shall be connected to the supply via an appropriate switched fused double pole isolat...

Страница 5: ...ructure The height between the ceiling face and the top of the air curtain case needs to be adjusted to circa 140mm to enable the grille assembly to fit flush with the ceiling Adjust accordingly After...

Страница 6: ...d eg BMS then the heat output can be selected by connecting the appropriate terminals WIRED TERMINALS RAC0603 RAC0604 RAC1006 H1 H2 F 3000W 4500W 6000W H1 F 1000W 1500W 2000W H2 F 2000W 3000W 4000W Pl...

Страница 7: ...trical connections for wireless control models To switch on the appliance and operate the blower depress the left hand switch marked FAN When the centre switch only marked with a single bar is depress...

Страница 8: ...Maintenance 7 4 Fault Conditions If the heater will not operate disconnect it from the mains and arrange for a certified electrician to attend to investigate the reason 7 5 Replacing Fan Heater Assemb...

Страница 9: ...41001452 Iss 06 9...

Страница 10: ...41001452 Iss 06 10...

Отзывы: