The aircurtain can be also controlled by
mechanical switches.
In this configuration touchscreen controller
or BMS controls will not work.
To operate heater by mechanical switch-
es, the DIP switches on the main pcb
need to be set to 000X.
The DIP switch 4 is used to select fan
speed range.
For installation height of 2 - 3m set the DIP
switches to 0000.
For installation height of 3 - 4m set the DIP
switches to 0001.
SW1 - on / off
SW2 - low speed / high speed
SW3 - 1/3 heat output
SW4 - 2/3 heat output
CAT5 cable with RJ45 connectors can be
used to network up to 7 air curtains in a
daisy-chain configuration.
The 2 DIP switches on all 7 connected air-
curtains must be set to different addresses.
All possible addresses are:
1
100X
2
010X
3
110X
4
001X
5
101X
6
011X
7
111X