T H E C O N T I N U O U S P O W E R C O M P A N Y
Page 14
SPECIFICATIONS
ELECTRICAL S1500-601
Input
Voltage (Auto-selectable)
120
~
or
240
~
+10%, -20%
(without Battery discharge)
Power Factor Corrected
IAW
MIL STD. 1399 Sec. 300
Frequency
50Hz / 60Hz
Current
15.6A @ 120V
~
7.8A @ 240V~
Output
Voltage
120
~
±
3%
Frequency
50Hz / 60Hz (software select)
Line Sync (software select)
Current
12.5A @ 100% non linear load
Power
1500VA, 1050W, 0.7pf
Crest Factor Ratio
(Non-linear load and
less than 5% THD) Typical
@50% Load Up to 4.8:1
@75% Load Up to 3.2:1
@100% Load Up to 2.4:1
Total Harmonic Distortion (THD)
3% Typ; 5% Max.
(@100% Non-linear load)
Dynamic Response
±
4% for 100% Step Load
Change,
0.5 Millisecond Recovery Time
Overload
110% for 10 Minutes;
200% for 0.5 Seconds
Efficiency (UPS)
85% Typ.
Batt Back-up (Full load\Half load)
5min\17min
UPS Protection
Input and Output Short Circuit;
Input and Output Overload;
Excessive Battery Discharge
ENVIRONMENTAL
Operating Temperature
32
o
F to 104
o
F (0
o
C to 40
o
C)
Humidity
0% to 95% Non-condensing
Altitude
Sea Level to 10,000 Feet
Audible Noise
39-42 dBA at Five Feet
MECHANICAL
Input Inlet (6’ Line Cord Provided)
L5-20 Plug(120V~) or L6-15
Plug(240V~) to IEC320
Output (Qty.)
(1) Duplex 5-15R
Cooling
Low Velocity, Temperature
Controlled Reversible Forced
Air
Dimensions HxWxD in(cm)
14.1(36) x 6.9(17.5) x 21(53)
Weight lbs (kg)
80 (36)
DESIGN
Standard Features
Power Factor Corrected, Digital
Regenerative
™
On-Line, Sinewave
Inverter Powers Load Continuously
Extended Brownout Protection
Designed for Non-linear Loads
Continuous Operation on
-20%,+12% Line
Automatic Bypass
RS232 Data Interface
Software Selectable Output
Frequency
AC Output Switch
Auxiliary Battery Connector
Optional SNMP Interface
Specifications UL60601-1
Design
FCC Class A
IEEE 587/ANSI C62.41
MTBF
In Excess of 100,000 Hours
Typical Recharge Time to
85% Capacity at 100% Load
8 Hours
CONTROLS AND INDICATORS
Visual Indicators
Sequenced LEDs
Single LED
Battery Level, Load Level
AC Input, Inverter On, Fault
Fault Silent, AC Output,
Cold Start, Replace Battery
Front Panel Controls
Power On, Cold Start
Fault Silence, Battery Test
AC Output On/Off
Audible Alarms
Utility Interrupt, Inverter Failure
Overload, Low Battery
RS232 Data Interface (DB-9F)
Full Interactive, Remote Computer
Monitoring and Control of UPS
Functions.
Compatible with Systems
Enhancement UPS Monitor &
Control Software
Open-Collector (DB-9F)
Allows Alarm Function Monitoring
Optional SNMP Interface
(RJ45)
Allows Full Control and Monitoring
Over Network Connection.
Specifications subject to change without notice.
7/04