The Input Setup screen shown in
allows for input settings to be entered such as channel
assignment, scaling, engineering units, and more.
Figure 4.23
The Channel Offset page shown in
allows the engineering value from the input to be
increased or decreased by a fixed amount. For example, if the currently measured value is 5 psi but a
mechanical gauge indicates it should be 7 psi, a targeted new value of 7 psi may be entered which will
offset the measured value by 2 psi from now on.
Figure 4.24
Channel
transmitter is
wired to
Type of signal
from
transmitter
Engineering
units to be
displayed
Decimals to
be displayed
Minimum and
maximum
scaling value
Smooths bounce
in signal. High
filter removes
bounce but
slows response.
Must be
between 0-99%
Opens “channel offset”
Opens “retransmission”
Turns the
channel offset
on/off
Value
currently
measured
New value to
adjust input
too.
Type of units
to be selected.
Only shown in
Spare Setup.