11
Cable or Conduit Entry
The unit enclosure is provided with ½” NPT entry holes fitted with liquid-tight cable grips for use
with outdoor use cables (by installer) for power and DMX connection. The recommended
torque for these cable grips is as follows:
Locking
Nut
40
‐
45
inch
pounds
Sealing
Nut
50
‐
55
inch
pounds
If outdoor use conduit is used instead, it is recommended that the conduit be sealed after
installation to prevent moisture entry, including free air exchange, in order to minimize the
chance of condensation buildup.
Mains Wire Installation and Termination
Install the mains cable or conduit in the entry provided as shown in the drawing below. A liquid
tight cable grip is provided for use with suitable outdoor rated cable with diameter range of
.170”/4,3mm - .450”/11,4mm.
When cable is used, strip outer jacket 6”/150mm.
The mains connection is a 3 pos. plug/socket type terminal block which may be disconnected
for ease of assembly. Strip insulation from individual conductors .25”/7mm and terminate in the
provided screw terminal socket (see illustration above) Mains terminations are ash shown and
are marked on the unit.
DMX512 Wire Termination
The SHoW DMX Vero Net Transceiver is provided with a PCBA mount terminal block for DMX
connection (see illustration above). DMX Input / Output connections are as shown and are
marked on the unit.