8-2 In Case of Trouble
Trouble
Check
Power does not turn ON.
Is the power supply connected properly?
Is power being supplied properly?
Has the connection been made with the polarity (+/
−
) reversed?
Is the appropriate power voltage used?
Is there sufficient current capacity?
The measured value
remains unchanged.
Is a hold signal being input?
When a hold signal is being input, “HOLD” is displayed in the
upper right corner of the display.
Turn the power OFF, then disconnect and re-connect the detector.
Inaccurate
Is the detector installed securely with no play?
Is the measurement terminal loose?
Is the detector being subjected to any excessive vibration or impact?
For example, when a detector is put on a guide rail and moved up
and down by an air cylinder, the impact from a strong collision with
the mechanical stopper on the upper edge (back clearance side)
may cause erroneous counting.
Install a shock absorber or other means of softening the impact,
reduce the air cylinder operation speed, or take other appropriate
measures.
Is the spindle moving up and down properly?
If the spindle is tightened excessively during installation, it may affect
spindle operation.
Keys do not respond to
input.
Are the keys locked?
To unlock the keys, simultaneously hold down the [SET],
[P-CLEAR] and [RESET] keys for about 3 seconds.
Turn the power OFF, wait a few seconds, and then turn the power
back ON.