Single valve installations
Connect the spade connectors from any sensor unit to the solenoid
tabs taking care to connect the wires according to the label. The
solenoid cables are orange and turquoise. If these are not long enough
they can be extended by up to 10 metres.
NB:
Should you require extension cables for the solenoid
valves please contact Cistermiser technical services.
Multiple valve installations
Up to 3 valves can be connected in parallel using the ‘daisy chain’ cable
provided in the additional solenoid valve kit (AVK). The AVK is available
from Cistermiser or any major plumbing merchant. Ensure that like
colours are connected. Use the ‘piggy back’ connectors to loop 2 or 3
valves together as shown opposite.
Valve
installation
C
D
SZ/LFC
Installation
The SZ/LFC must be connected to the SZ/IF; this can be directly to one of the 2 output cables on the SZ/IF or via an
extension”Y” cable supplied with an additional sensor kit. If required this cable can be extended up to a maximum length of
100m with 1.5mm² cable.
1. Secure the SZ/LFC to a solid surface either with screws or the sticky pads provided.
2.
Remove the top cover and pierce the appropriate rubber cable gland to connect the lights and/or fans. Take care
when piercing the gland not to damage the product.
WARNING:
Isolate mains supplies to lights and fans
3. Connect the live feed for the lights to the LIGHTS contactor (Ensure load does not exceed 8A)
4. Connect the live feed for the fans to the FAN contactor (Ensure load does not exceed 8A)
5. Replace lid with screws provided before restoring power.
WARNING:
This is a functional switching device, and must not be used for safety or maintenance isolation!
WARNING:
This device is intended for use with hazardous voltages. The installation and maintenance of this device
must be carried out by a qualifi ed electrician in accordance with local wiring regulations. Before installing
this device, please read these installation instructions carefully.
NB:
Do not install near localised heat source
NB:
Where necessary use wiring conduit to protect exposed cables
8
0118 969 1611 | [email protected] | www.cistermiser.co.uk
NB:
Valves can be connected to any sensor. Maximum 3 valves per system.
NB:
For grey water/rain water harvesting. Ensure adequate fi ltering is fi tted, a 10µm fi lter is recommended.
NB:
For chemical water treatment. If the water system has been treated with chemical dosing, ensure the system is
thoroughly fl ushed before fi tting any Cistermiser products. Concentrated chemicals in dead legs can damage the
product and result in failure. If the water is treated with Chlorine Dioxide (ClO2), concentration levels are maintained
below 5ppm.
NB:
As with all water containing products, lime scale in hard water areas can affect the products performance. This can
result in maintenance to remove the lime scale as and when required.
Install valve on to the water supply leading into the washroom (hot, cold
and rain/grey water) or as close as practically possible to the entry point
to suit the pipe layout.