Page 18
S6162-BS-MMC-010/12489
For ductwork less than 14 feet and 2 elbows equivalent and less than 0.3 inches static
pressure:
NEVER exhaust the dryer into a chimney.
NEVER install wire mesh screen over the exhaust or make-up air area.
NEVER exhaust into a wall, ceiling, or concealed space.
1.
Make-Up Air opening from outside the building may enter the enclosure from the top or side
walls. The area of the opening should be equal to 4 to 6 times the sum of the dryer duct areas.
Provide
1
square
foot
(.1m²)
for
each
6
inches
(15.24
cm)
diameter;
2
square
feet
(.2m²)
for
each
8 inches (20.3 cm) diameter; and 4 square feet (.4m²) for each 12 inches (30.5 cm) diameter.
2.
Enclosure (plenum) with service door. This separates the dryer air from the room comfort air. If
dryers use room air instead of outside air, additional heat loss can be another 25 BTU/HR (6.3
kcal/hr)
for
each
cubic
foot
per
minute
(CFM)
(.03m³/min.)
used.
3.
Zero inches (mm) clearance to combustible material allowed on sides and at points within 4
inches (100 mm) of front on top.
4.
Heat loss into laundry room from dryer front panels is about 60 BTU/HR per square foot (15
kcal/hr
per
0.1m²).
DRYER INSTALLATION WITH SEPARATE EXHAUST
( P R E F E R R E D )
Содержание L36TD30ME
Страница 10: ...Page 10 S6162 BS MMC 010 12489...
Страница 20: ...Page 20 S6162 BS MMC 010 12489 RECOMMENDED STEAM PIPING INSTALLATION ILLUSTRATION...
Страница 40: ...Page 40 S6162 BS MMC 010 12489 BACK CHANNEL BOLTED ASSEMBLY TU10600...
Страница 50: ...Page 50 S6162 BS MMC 010 12489...
Страница 51: ...Page 51 S6162 BS MMC 010 12489...
Страница 52: ...Page 52 S6162 BS MMC 010 12489...
Страница 53: ...Page 53 S6162 BS MMC 010 12489...