DRYER INSTALLATION WITH SEPARATE EXHAUST (PREFERRED)
DRYER INSTALLATION WITH SEPARATE EXHAUST
(PREFERRED)
For Exhaust Duct less than 14 feet (5 m) and 2 elbows equivalent
and less than 0.3 (8 mm) inches static pressure.
NEVER exhaust the dryer into a chimney.
NEVER install wire mesh screen over the exhaust or make-up
air area.
NEVER exhaust into a wall, ceiling, or concealed space.
1. Make-up air opening from outside the building may enter the
enclosure from the top or side walls.
(See Dryer Make-Up Air
Requirements Chart)
2. Enclosure (plenum) with service door. This separates the dryer air
from the room comfort air. If dryers use room air instead of
outside air, the heat loss can be another 25 Btu/h (6.3 kcal/h) for
each cubic foot per minute (cfm) used.
EXAMPLE:
A 125 lb. dryer with 2000 cfm (3400 m
3
/h) = heat
loss of 50,000 Btu/h (12,600 kcal/h).
3. Zero inches clearance to combustible material allowed on sides
and at points within 4 inches (102 mm) of front on top.
4. Heat loss into laundry room from dryer fronts
only
is about
60 Btu/h (15.2 kcal/h) per square foot.
DRYER INSTALLATION
WITH SEPARATE
EXHAUST (PREFERRED)
Содержание HD170
Страница 12: ...Page 12 GAS DRYER DIMENSIONS ...
Страница 13: ...Page 13 STEAM DRYER DIMENSIONS ...
Страница 18: ...Page 18 GAS PIPING INSTALLATION ILLUSTRATION ...
Страница 26: ...Page 26 DRYER INSTALLATION WITH MULTIPLE EXHAUST ILLUSTRATION ...
Страница 33: ...Page 33 OPERATING INSTRUCTIONS TWO TIMER MODELS ...
Страница 41: ...Page 41 DIRECT SPARK IGNITION OPERATION FLOW CHART ...
Страница 43: ...Page 43 BURNER AIR INLET ADJUSTMENT BURNER AIR INLET ADJUSTMENT ...
Страница 44: ...Page 44 BASKET ALIGNMENT FOR DRYERS WITH TM200 GEAR REDUCER ...
Страница 53: ...Page 53 REAR VIEW TM200 GEAR REDUCER See following page for partnumbers ToGearM otor ...
Страница 55: ...Page 55 REAR VIEW GEAR MOTOR See following page for partnumbers ToGearM otor ToFanM otor ...
Страница 75: ...Page 75 ...