Page 25
DRYER INSTALLATION WITH MULTIPLE EXHAUST
For Exhaust Duct less than 14 feet (5 m) and 2 elbows
equivalent and less than 0.3 inches (.8 mbar) static pressure.
DRYER EXHAUSTS
Area of section “A-A” must be equal to the sum of dryer exhaust pipes
entering multiple exhaust pipe. (
See chart below.
)
MODELS:
HD150
No. of Dryers
Duct Diameter
(in inches)
(in CM)
1
2 3
4
5
6
7
8
9 10 11 12
12 17 21 24 27 30 32 34 36 38 40 42
30 43 53 61 68 76 81 86 91 97 100 106
Содержание HD170
Страница 12: ...Page 12 GAS DRYER DIMENSIONS ...
Страница 13: ...Page 13 STEAM DRYER DIMENSIONS ...
Страница 18: ...Page 18 GAS PIPING INSTALLATION ILLUSTRATION ...
Страница 26: ...Page 26 DRYER INSTALLATION WITH MULTIPLE EXHAUST ILLUSTRATION ...
Страница 33: ...Page 33 OPERATING INSTRUCTIONS TWO TIMER MODELS ...
Страница 41: ...Page 41 DIRECT SPARK IGNITION OPERATION FLOW CHART ...
Страница 43: ...Page 43 BURNER AIR INLET ADJUSTMENT BURNER AIR INLET ADJUSTMENT ...
Страница 44: ...Page 44 BASKET ALIGNMENT FOR DRYERS WITH TM200 GEAR REDUCER ...
Страница 53: ...Page 53 REAR VIEW TM200 GEAR REDUCER See following page for partnumbers ToGearM otor ...
Страница 55: ...Page 55 REAR VIEW GEAR MOTOR See following page for partnumbers ToGearM otor ToFanM otor ...
Страница 75: ...Page 75 ...