1-33
Cisco ONS 15454 DWDM Procedure Guide, Release 9.2
78-19286-01
Chapter 1 Install the Cisco ONS 15454 Shelf Assembly
Required Tools and Equipment (ETSI)
NTP-G7 Install the Power and Ground
Warning
Before performing any of the following procedures, ensure that power is removed from the DC circuit.
Statement 1003
Warning
This equipment is intended to be grounded. Ensure that the host is connected to earth ground during
normal use.
Statement 39
Warning
Use copper conductors only.
Statement 1025
Purpose
This procedure installs power feeds and grounds the ONS 15454.
Tools/Equipment
ANSI and ETSI:
•
#2 Phillips Dynamometric screwdriver
•
Medium slot-head screwdriver
•
Small slot-head screwdriver
•
Screws
•
Ground cable 13.3-mm² (#6 AWG) stranded
•
Listed pressure terminal connectors such as ring and fork types;
connectors must be suitable for #10 AWG copper conductors
•
Wire cutters
•
Wire strippers
•
Crimp tool
•
Fuse panel
ANSI only:
•
Power cable (from fuse and alarm panel to assembly), #10 AWG,
copper conductors, 194 degrees F [90 degrees C])
•
Wire wrapper
ETSI only:
•
Power cable (from fuse panel to MIC-A/P and to MIC-C/T/P), shipped
with the ONS 15454 ETSI
•
Two-hole grounding lug, shipped with the ONS 15454 ETSI
Prerequisite Procedures
NTP-G4 Open and Remove the FMEC Cover (ETSI Only), page 1-26
NTP-G6 Install the MIC-A/P and MIC-T/C/P FMECs (ETSI Only),
page 1-31
NTP-G5 Remove the Backplane Covers (ANSI Only), page 1-29
Required/As Needed
Required
Onsite/Remote
Onsite
Security Level
None
Содержание ONS 15454
Страница 48: ...Tables xlviii Cisco ONS 15454 DWDM Procedure Guide Release 9 2 78 19286 01 ...
Страница 58: ...Procedures lviii Cisco ONS 15454 DWDM Procedure Guide Release 9 2 78 19286 01 ...
Страница 78: ...Tasks lxxviii Cisco ONS 15454 DWDM Procedure Guide Release 9 2 78 19286 01 ...
Страница 85: ...lxxxv Cisco ONS 15454 DWDM Procedure Guide Release 9 2 78 19286 01 Preface ...
Страница 87: ...lxxxvii Cisco ONS 15454 DWDM Procedure Guide Release 9 2 78 19286 01 Preface ...