Figure 28: Inserting the Fabric Module into the Chassis
Handles spring out from the module.
3
Align the module with the guides in the open slot
and push the module half way into the slot.
1
Press both eject buttons.
2
e) With your face away from the fabric module, press both ejector buttons on the front of the module.
Keep your face at least 12 inches (30 cm) from the front of the fabric module so that the ejector handles
do not hit your face when they spring out from the front of the module.
Caution
Both ejector handles spring out from the front of the module (see Callout 2 in the previous figure).
f)
Grasp both handles, fully rotate the levers 90 degrees from the front of the module, and push the module all the way
into the slot until it seats.
The front of the module will be about 1/4 inch out from the installed fabric modules.
g) Simultaneously rotate both handles to the front of the module while pressing the module further into the slot (see
Callout 1 in the following figure).
The handles click when fully rotated to the front of the module.
Cisco Nexus 7710 Switch Site Preparation and Hardware Installation Guide
OL-30452-01.
126
Installing or Replacing Modules, Fan Trays, and Power Supplies
Installing or Replacing a Fabric Module