Full Redundancy
Mode
Input Source
Redundancy
Mode
Power Supply
Redundancy
Mode
Combined Mode
Power Supplies
Power Inputs
—
—
—
3500 W
1
1 input (277 V)
3500 W
3500 W
3500 W
7000 W
2
3500 W
3500 W
7000 W
10,500 W
3
7000 W
7000 W
10,500 W
14,000 W
4
—
—
—
3500 W
1
1 input (220/230
V)
3500 W
3500 W
3500 W
7000 W
2
3500 W
3500 W
7000 W
10,500 W
3
7000 W
7000 W
10,500 W
14,000 W
4
—
—
—
3100 W
1
1 input (210 V)
3100 W
3100 W
3100 W
6200 W
2
3100 W
3100 W
6200 W
9300 W
3
6200 W
6200 W
9300 W
12,400 W
4
—
—
—
1500 W
1
1 input (110 V)
1500 W
1500 W
1500 W
3000 W
2
1500 W
1500 W
3000 W
4500 W
3
3000 W
3000 W
4500 W
6000 W
4
A combination of 3-kW AC and 3.5-kW HVAC/HVDC power supplies can be used.
Note
Maximum Power Available for 3.5-kW Inputs (DC)
The maximum power available for operations depends on the input power from your power source, the number
and output capabilities of your power supplies, and the power redundancy mode that you use. The following
table lists the amount of power available for 3.5-kW HVAC/HVDC power supplies depending on DC power
inputs, number of power supplies, and the mode used.
Cisco Nexus 7706 Hardware Installation Guide
OL-31330-01
76
Managing the Switch
Maximum Power Available for 3.5-kW Inputs (DC)
Содержание Nexus 7706
Страница 8: ...Cisco Nexus 7706 Hardware Installation Guide OL 31330 01 viii Contents ...
Страница 26: ...Cisco Nexus 7706 Hardware Installation Guide OL 31330 01 14 Preparing the Site Clearance Requirements ...
Страница 170: ...Cisco Nexus 7706 Hardware Installation Guide OL 31330 01 158 Switch Specifications Switch Specifications ...
Страница 178: ...Cisco Nexus 7706 Hardware Installation Guide OL 31330 01 166 LEDs Power Supply LEDs ...
Страница 190: ...Cisco Nexus 7706 Hardware Installation Guide OL 31330 01 IN 4 INDEX ...