![Cisco Catalyst 9600 Series Скачать руководство пользователя страница 99](http://html.mh-extra.com/html/cisco/catalyst-9600-series/catalyst-9600-series_hardware-installation-manual_65943099.webp)
Chassis and Module Power and Heat Values
The following tables provide the power and heat dissipation data. Unless otherwise noted, the information in
the tables is measured under fully loaded conditions (transceivers installed).
DC output power is the output from the power supply (internal to the system). The AC-input power is the
input from the outlet to the power supply. The percentage difference between the two values is the efficiency
of the power supply.
Note
Table 9: Power Requirements and Heat Dissipation - Fan Tray
Heat Diss.
in BTU /
hr.
Current @ 240V
Current @
180V
Current @
120V
Current @
90V
DC-Output in
Watts
(Power
Requested)
AC-Input
Power in
Watts
(Power
Allocated)
PID
1706
2.1
2.8
4.2
5.6
450
500
C9606-FAN
Table 10: Power Requirements and Heat Dissipation - Supervisor Module
Heat Diss. in
BTU / hr.
Current @
240V
Current @
180V
Current @
120V
Current @
90V
DC-Output in
Watts
(Power
Requested)
AC-Input
Power in
Watts
(Power
Allocated)
PID
2942
3.6
4.8
7.2
9.6
775
862
C9600-SUP-1
Table 11: Power Requirements and Heat Dissipation— Line Cards
Heat Diss. in
BTU / hr.
Current @
240V
Current @
180V
Current @
120V
Current @
90V
DC-Output in
Watts
(Power
Requested)
AC-Input
Power in
Watts
(Power
Allocated)
PID
874
1.1
1.5
2.2
2.9
230
256
C9600-LC-48YL
761
1
1.3
1.9
2.5
200
223
C9600-LC-24C
Cisco Catalyst 9600 Series Switches Hardware Installation Guide
95
Technical Specifications
Chassis and Module Power and Heat Values
Содержание Catalyst 9600 Series
Страница 104: ...Cisco Catalyst 9600 Series Switches Hardware Installation Guide 100 LEDs Line Card LEDs ...
Страница 110: ......