Cabling the Power Filter Units
Power Considerations ▀
ASR 5000 Installation Guide ▄
147
Power Cable Requirements
You can install up to three chassis in an equipment rack or telecommunications cabinet. Typically power cabling is run
from the office Power Distribution Frame (PDF) to a Power Distribution Panel (PDP) installed in the rack or cabinet and
then to each of the chassis. Due to the required bending radius at each of the system’s PFUs, distributing power through
a PDP allows you to use a smaller, more flexible cable for each chassis.
The following table identifies the recommended gauges for power cables.
Table 47.
Recommended Cable Gauge Information
Termination
Conductor Sizing Information
PDF to Fuse Panel
Assuming an 80-foot (24 meter) loop length, each cable between the PDF and PDP must be
the equivalent of 350,000 circular mils or greater.
Calculations assume a 0.3 volt drop from the PDF to the PDP, and a 0.3 volt drop from the
PDP to the chassis. This is a total voltage drop of 0.6 volts.
Fuse Panel to ASR 5000
Assuming an 18-foot (5.5 meter) loop length, each cable between the PDP and the chassis
must be the equivalent of 83,690 circular mils (1 AWG) or greater. Use high-flex cable.
Calculations assume a 0.3 volt drop from the PDF to the PDP, and 0.3 volt drop from the fuse
panel to the chassis. This is a total voltage drop of 0.6 volts.
The following figure and table provide details for wiring the PFUs.
Содержание ASR 5000 Series
Страница 9: ...Contents ASR 5000 Installation Guide ix Spare Component Recommendations 317 ...
Страница 10: ......
Страница 14: ......
Страница 54: ......
Страница 64: ......
Страница 90: ......
Страница 104: ......
Страница 122: ......
Страница 126: ......
Страница 148: ...Cabling the Power Filter Units Power Considerations ASR 5000 Installation Guide 148 Figure 49 PFU Wiring Diagram ...
Страница 186: ......
Страница 194: ......
Страница 206: ......
Страница 228: ......
Страница 276: ......
Страница 284: ......
Страница 290: ......
Страница 300: ...RoHS Compliance Statement Chassis ASR 5000 Installation Guide 300 Chassis ...
Страница 301: ...RoHS Compliance Statement Fan Assembly ASR 5000 Installation Guide 301 Fan Assembly ...
Страница 302: ...RoHS Compliance Statement Power Filter Unit PFU ASR 5000 Installation Guide 302 Power Filter Unit PFU ...
Страница 303: ...RoHS Compliance Statement Full Product ASR 5000 Installation Guide 303 Full Product ...
Страница 304: ...RoHS Compliance Statement Full Product ASR 5000 Installation Guide 304 ...