----------- TCP2RS -------------- User’s manual -------------------- page 21/43
21
4.5.6 Remote IP Address
Selecting Autostart (automatic connection) in Connect Mode makes a connection to this
IP address on the network. This is the destination IP address used with an outgoing
connection.
4.5.7 Remote Port
The remote TCP port number must be set to use automatic connections. This parameter
defines the port number on the target host to which a connection is attempted.
Note:
To connect an ASCII terminal to a host using the
TCP2RS
for login
purposes, use the remote port number 23 (Internet standard port
number for Telnet services).
4.5.8 Disconnect Mode
In Disconnect Mode, DTR drop either drops the connection or is ignored.
Table 4-7:
Disconnect Mode Options
Option
Bit 7
6
5
4
3
2
1
0
Disconnect
with
DTR
drop
1
Ignore DTR
0
Telnet
mode
and
terminal
type
setup
1
Channel (port) password
1
Note:
See Appendix B for information on converting binary values to
hexadecimal format.
4.5.9 Flush Mode (Buffer Flushing)
Using this parameter, you can control line handling and network buffers with connection
startup and disconnect. You can also select between two different packing algorithms.
Table 4-8:
Flush Mode Options
Function
Bit 7
6
5
4
3
2
1
0
Input Buffer (Serial to Network)
Clear
active
connection
(from
serial)
1
Clear
passive
connection
(from
network)
1
Clear
at
disconnect
1
Output Buffer (Network to Serial)