---------      EARTH RESISTANCE TESTER   

T-3V

      -------   Page  No.    6 

 - 

 

 

 

3.2.- Use 

 
Before starting measurements, carefully read the Safety Advice section. 

ƒ

  Connecting the test pins: 

Connect the green, yellow and red test pins to the terminals E, P and C with the 
earth rods P1, C1 placed in the  ground "in a straight line" (see figure). 

ƒ

  Place the function switch [7] onto the ACV position and ensure that the voltage 

reading is less than 10 V AC. If not the accuracy of the earth resistance 
measurement cannot be guaranteed. 

 

If the PUSH-ON [9] button is pressed and the operating indicator [2] does not 
come on, thisl means that there is an open circuit between the test pins. 

 

200V

~

5 10m

~

5 10m

~

 

 

ƒ

  Place the range switch [8] on the appropriate scale and the function switch [7] 

on position "

". Then press PUSH-ON [9] and TIMER ON10] at the same time 

and read the value on the indicator. 

NOTE: 

When none of the E, P and C terminals is connected to the test pins, a 
reading between 300 and 600 is normal (in function 

, range 2 k

). 

 

Red 
Yellow 
Green 
 
EARTH 

Содержание T-3V

Страница 1: ...EARTH RESISTANCE TESTER T 3V Code M80410 INSTRUCTION MANUAL M98111001 03 04A CIRCUTOR S A...

Страница 2: ...he batteries 7 4 2 Cleaning and storage 7 4 3 5 TECHNICAL SERVICE 7 SAFETY ADVICE Before handling the equipment read the instruction manual and in particular the SAFETY ADVICE section The symbol on th...

Страница 3: ...to measure earth voltage The 2 mA measurement current allows floor resistivity to be tested without tripping the earth circuit breakers in the circuit to be checked Battery operation Self disconnectin...

Страница 4: ...EN61010 Battery low indicator The symbol B appears on the display Reading memory indicator The symbol DH appears on the display Over range indicator 1 in the most significant digit MSD Open circuit in...

Страница 5: ...operating conditions 1 INDOOR USE 2 Category III Installation 3 Degree of Pollution 2 4 Altitude up to 2 000 m 5 Max relative humidity 80 6 Ambient temperature 0 40 C WARNING Handle the rods without...

Страница 6: ...e controls and the parts 1 Female connector for earth connection 2 Operating open circuit indicator 3 Reading memory switch 4 Timer deactivation button 5 LCD Display 6 Female connectors for line condu...

Страница 7: ...han 10 V AC If not the accuracy of the earth resistance measurement cannot be guaranteed If the PUSH ON 9 button is pressed and the operating indicator 2 does not come on thisl means that there is an...

Страница 8: ...crew 4 2 Cleaning and storage Warning Avoid water getting into the case to prevent electrical discharge or damage to the tester Periodically clean the case with a soft cloth dampened with water and de...

Отзывы: