4�7�2�- MODBUS pROTOCOL
The
DHB-324
uses the RTU mode (Remote Terminal Unit) with its Modbus protocol.
The
M
odbus functions implemented in the unit are as follows:
function
03
for reading n records.
function
06
for writing one record.
function
16
for writing multiple records
function
17
for identifying the slave unit.
The maximum response time is 1000 milliseconds.
4�7�3- MODBUS MeMORy MAp
Modbus addresses are in decimal format.
Table 7:Type of values in the Modbus memory MAp�
Address
Type of value
Description
4000-4100
integer (16 bits)
Value given in a 16-bit record.
7000-7199
float (32 bits)
Value given in two consecutive 16-bit records.
The records include the same data as the 32-bit records in the
7500 area.
Records valid for read function only.
7200-7400
float (32 bits)
Value given in two consecutive 16-bit records.
The records include the same data as the 32-bit records in the
7600 area.
The read and write functions are valid for the records.
7500-7599
float (32 bits)
Value given in a 32-bit record.
Records valid for read function only.
7600-7700
float (32 bits)
Value given in a 32-bit record.
The read and write functions are valid for the records.
49
Instruction Manual
DHB-302 DHB-324
Содержание DHB-302
Страница 1: ...INSTRUCTION MANUAL M044B01 03 17A Single phase Vac analyzer DHB 302 DHB 324...
Страница 2: ...2 DHB 302 DHB 324 Instruction Manual...
Страница 64: ...Figure 60 Dimensions of the DHB 3xx 64 DHB 302 DHB 324 Instruction Manual...
Страница 66: ...8 CE CERTIFICATE 66 DHB 302 DHB 324 Instruction Manual...
Страница 69: ...69 Instruction Manual DHB 302 DHB 324...