6�2�- MODBUS PROTOCOL
In the Modbus protocol, the
CVM-D41 DC
device uses the RTU (Remote Terminal Unit) mode.
The Modbus functions implemented in the device are as follows:
Function 0x01
:
Reading a relay.
Function 0x02
:
Reading input status.
Function 0x03
and
0x04
:
Reading integer registers.
Function 0x05
: Writing a relay.
Function 0x0F
:
Writing multiples relays
Function 0x10
: Writing multiples registers.
6�2�1� READING EXAMPLE: FUNCTION 0x01�
Question:
Status of output relays
Address
Function
Initial
Register
No� of
Registers
CRC
01
01
0000
0002
BDCB
Address: 01
, Peripheral number: 1 in decimal.
Function: 01
, Read function.
Initial Register: 0000
, on which the reading will start.
No� of Registers: 0002
, number of registers read.
CRC: BDCB
, CRC Character.
Response:
Address
Function
No� of Bytes Register No� 1 Register No� 2
CRC
01
01
01
0001
0000
6611
Address: 01
, Responding peripheral number: 1 in decimal.
Function: 01
, Read function.
No� of bytes: 01
, No. of bytes received.
Registre No 1: 0001
, output relays 1 closed.
Registre No 2: 0000
, output relays 1 open.
CRC:6611
, CRC.Character.
6�2�2� EXAMPLE OF OPERATION OF THE REMOTE CONTROL: FUNCTION 0x05�
Question:
Activate the output of relay 1, programmed to work in remote control mode.
Address
Function
Initial
Register
Relay action
CRC
01
05
0000
FF00
8C3A
Address: 01
,
Peripheral number: 1 in decimal.
Function: 05
,
Writing a relay
Initial Register: 0000
, relay 1 address.
Relay action: FF00
, We indicate that we want to close the relay.
Содержание CVM-D41 DC
Страница 1: ...INSTRUCTION MANUAL Power analyzer CVM D41 DC M337B01 03 22A ...
Страница 2: ...2 CVM D41 DC Instruction Manual ...
Страница 55: ...55 Instruction Manual CVM D41 DC 10 EU DECLARATION OF CONFORMITY ...
Страница 56: ...56 CVM D41 DC Instruction Manual ...
Страница 57: ...57 Instruction Manual CVM D41 DC ...