23
Instruction Manual
computer MAX
This parameter permits the adaptation of the regulator to different options of connection of
voltage and current measurement in the three phase system. The default assumed connection
is the one shown in
Figure 4
and
Figure 5
,
i.e., the current transformer placed in phase L1 and
voltage measurement between phases L2 (terminal C) and L3 (terminal D).
Sometimes it’s difficult to guarantee this connection or even check how it is. To adapt to this
unknown situations the
computer MAX
devices allow the selection of different options, T1 to
T6, as shown in
Table 12
.
To select the right option during start up, you should verify that there
is load and that the loads are mainly inductive with a cos
j
between 0,7 y 1. In this situation try
the different options until the cos
j
screen shows a value between 0,7 and 1.
Table 12: Phase shift options in computer MAX
Screen
U-I phase shift
at cos
j
=1
V measured in
phases
CT placed in phase
T1
30º
L3-L2
L3
T2
270º
L3-L2
L1
T3
150º
L3-L2
L2
T4
210º
L3-L2
L3 (P1-P2 or S1-S2 reversed)
T5
90º
L3-L2
L1 (P1-P2 or S1-S2 reversed)
T6
330º
L3-L2
L2 (P1-P2 or S1-S2 reversed)
6�1�9�-
PROGRAMMING THE CT RATED CURRENT (PRIMARY)�
The set-up of this parameter can be selected at the bottom of the menu options. Use the
keys until the bottom red LED
is flashing and push
.
The display will show the assumed CT primary current. Set the value according to the CT used
to measure installation current. The adjustment range is from 0 to 999 and with the x10 option
allows a rated primary current up to 9990 A. By default the secondary of CT is assumed to be
5 A.
6.2.- SET-UP MENU AND PROCEDURE
6�2�1�- HOW TO ACCESS THE SET-UP MENU
To access the set-up menu, press the key
for more than 1s (This is designated as long push
in
Table 13
, which gives a summary of the set-up procedure). The pointer starts blinking and
points to the parameter to be adjusted. Select the parameter by means of the keys
.
After the long push and in case that all the capacitor stages are disconnected, the device
jumps to the set-up status. In case that there are some stages connected, keep the key
pushed while the regulator disconnects the connected stages sequentially and respecting the
programmed delay time. Once all the stages have been disconnected the device enters the
set-up status and allows the adjustment of the different parameters.
A schematic diagram of the set-up menu showing the different navigation paths is shown in
Table 13�
The meanings of the different adjustable parameters have been explained in
“6.1.-
CONFIGURABLE PARAMETERS”
.
Содержание computer MAX 12
Страница 1: ...INSTRUCTION MANUAL Power factor regulators computer MAX 6 computer MAX 12 M98228201 03 17A...
Страница 2: ...2 computer MAX Instruction Manual...
Страница 30: ...30 computer MAX Instruction Manual 11 CE CERTIFICATE...
Страница 31: ...31 Instruction Manual computer MAX...
Страница 32: ...32 computer MAX Instruction Manual...
Страница 33: ...33 Instruction Manual computer MAX...