39
Instruction Manual
CBS-400B
Possible statuses of
CBS-400B
:
Table 13: Statuses of CBS-400B�
Possible statuses CBS-400B
Value
Description
0
Device in startup process
1
Device idle
2
Device tripped due to activation of the
TRIP
input
7�3�2�- CHANNEL VARIABLES
Function 0x04
: reading of registers, is used for these variables
Table 14: Modbus Memory Map: Channel variables�
Configuration variable
Format
Address
Units
Format
Channel 1
Channel 2 Channel 3 Channel 4
WGB
model
String
FA0-FA1
1068-1069 1130-1131
11F8-11F9
-
Serial no. of
WGB
String
FA2...FA8 106A...1070 1132.. 1138 11FA...1200
-
Firmware version (part 1)
Unit [16]
FA9
1071
1139
1201
-
Firmware version (part 2)
Unit [16]
FAA
1072
113A
1202
-
Firmware version revision
Unit [16]
FAB
1073
113B
1203
-
WGB
status
Unit [16]
FAC
1074
113C
1204
0��� 6
(see
)
WGB
channel
Unit [16]
FAD
1075
113D
1205
1:
channel 1
Programmed trip curve or de-
lay
Unit [16]
FAE
1076
113E
1206
ms
Programmed trip current
Unit [16]
FAF
1077
113F
1207
mA
Instant total leakage current
Unit [16]
FB0
1078
1140
1208
mA
Instant alternating leakage
current
Unit [16]
FB1
1079
1141
1209
mA
Instant direct leakage current
Unit [16]
FB2
107A
1142
120A
mA
Total leakage current that trip-
ped the relay
Unit [16]
FB3
107B
1143
120B
mA
Alternating leakage current
that tripped the relay
Unit [16]
FB4
107C
1144
120C
mA
Direct leakage current that
tripped the relay
Unit [16]
FB5
107D
1145
120D
mA
Programmed
prealarm current
Unit [16]
FB6
107E
1146
120E
%
Prealarm Operation
Unit [16]
FB7
107F
1147
120F
0:
Deactivated
1:
Activated with
deactivated latch
2:
Activated with
activated latch
Содержание CBS-400B
Страница 1: ...INSTRUCTION MANUAL Protection and monitoring relay CBS 400B M257B01 03 20A...
Страница 2: ...2 CBS 400B Instruction Manual...
Страница 50: ...50 CBS 400B Instruction Manual 11 CE CERTIFICATE...
Страница 51: ...51 Instruction Manual CBS 400B...
Страница 52: ...52 CBS 400B Instruction Manual...
Страница 57: ...57 Instruction Manual CBS 400B...