M039150CF
7
*
NOTE ON THE WORKING SERVICE: the control box automatically stops after 24h of continuous working. The control box
immediately starts up, automatically.
BURNER TYPE
HP72 MG.....1.50
HP72 MG......1.65
HP72 MG......1.80
Output
min. - max.
kW
330 - 1550
Fuel
Nat. gas - Light oil
Gas category
(
see next paragraph
)
Gas rate
min. - max. (Stm
3
/h)
35 - 164
Gas pressure.
min. - max. mbar
(
see Note 2
)
Light oil rate
min. - max. kg/h
28 - 131
Light oil train inlet pressure
max. bar
2
Oil viscosity
2 - 7.4 cSt @ 40°C
Oil density
840 kg/m3
Power supply
400V 3N ~ 50Hz
Total power consumption
kW
3.25
Fan motor
kW
2.2
Pump motor
kW
0.55
Protection
IP40
Approx. weight
kg
107
117
127
Operation
Double-stage
Gas Train
50
65
80
Valves size
/
Gas connection
2” / Rp2
2”
1/2
/ DN65
3” / DN80
Operating temperature
°C
-10 ÷ +50
Storage Temperature
°C
-20 ÷ +60
Working service
**
Intermitent
BURNER TYPE
HP73A MG.....50
HP73A MG.....65
HP73A MG.....80
Output
min. - max.kW
320 - 2300
Fuel
Nat. gas - Light oil
Gas category
(
see next paragraph
)
Gas rate
min. - max. (Stm
3
/h)
34 - 243
Gas pressure.
min. - max. mbar
(
see Note 2
)
Light oil rate
min. - max. kg/h
27 - 194
Light oil train inlet pressure
max. bar
2
Oil viscosity
2 - 7.4 cSt @ 40°C
Oil density
840 kg/m3
Power supply
400V 3N ~ 50Hz
Total power consumption
kW
3.5
Fan motor
kW
3
Pump motor
kW
0.55
Protection
IP40
Approx. weight
kg
112
122
132
Operation
Double stage
Gas train
50
65
80
Valves size
/
Gas connection
2” / Rp2
2”
1/2
/ DN65
3” / DN80
Operating temperature
°C
-10 ÷ +50
Storage temperature
°C
-20 ÷ +60
Working service
*
Intermittent
Note1:
All gas flow rates are referred to Stm
3
/h (1013 mbar absolute pressure, 15 °C temperature) and are valid for G20 gas (net
calorific value H
i
= 34.02 MJ/Stm
3
).
Note2:
Maximum gas pressure = 360mbar (with
Dungs MBDLE/MBC valves)
= 500mbar (with Dungs MBC or Siemens VGD gas valves).
Minimum gas pressure = see gas curves.