4 - Hydronic connection of the rough

 

(Drawings No 1 and 2)

Stretch the flexible hoses completely and form an arch 
to better adapt to necessary length when connecting. 
Connect  both  supplied  flexible  hoses  to  the  water 
inlets; Respect the inlet /outlet flow as per drawings.

Verify all hydronic connections and gaskets (Drawings 
No 1 and 2).

For  the  reversible  system,  insulate  the  gaskets  and 
flexible  hoses.  Connect  the  condensate  line  to  the 
waste  pipe;  use  a  condensate  draining  lifting  pump 
when necessary.

Mounting of draining / lifting pump

Place  the  support  of  the  pump  using  2  screws  of 
3x10mm

Glide the pump on the rubber-rail 
Connect the electrical plug.
Connect the air outlet
Connect  PVC  evacuation  tub  drain  pipe  6x9mm  / 
5/16” X 3/8”

Location at the bottom for electrical connection

Connection box, connecting terminal,
(see picture No 4)

Fixation for lifting pump only for reversible system

Picture No 1

Picture No 2

Picture No 3

Picture No 

4

Содержание Greenor

Страница 1: ...ty does not cover any damage arising from improper installation improper maintenance improper storage or handling Remove the Greenor fan coil from its box and separate the front panel from the rough c...

Страница 2: ...oil Use clean hands or clean thin rubber gloves to handle the panel Greenor fan coil must have at least a 6 15cm clearance on each side of the panel floor ceiling wall and at least 20 50cm in front of...

Страница 3: ...e in reversible mode To use with a reversible heat pump on a closed water circuit with a maximal service pressure 101 5 PSI 7bars and a maximal water temperature of 167 F 75 C and minimal water temper...

Страница 4: ...equate wall plugs and screws designed for the bearing wall The unit must be handled by two persons You may use an adapted lifting device Front View Rough Chassis Frontview Olycal Stone Frontplate 3 4...

Страница 5: ...he gaskets and flexible hoses Connect the condensate line to the waste pipe use a condensate draining lifting pump when necessary Mounting of draining lifting pump Place the support of the pump using...

Страница 6: ...Cable must not overhang from its protective ducting to prevent potential pinching by the front panel of the unit Make sure that power supply can be disconnected across all contacts Screw the cover bac...

Страница 7: ...perate the fan coil unit to check that all the fans function properly at the 3 operating speeds Check also that the opening of the thermal bypass valve opens correctly Once all these parameters have b...

Страница 8: ...regularly with a sweeper The panel can be cleaned with a slightly humid soft cloth or sponge with warm water and soap or a mild dish detergent Do not use abrasive or alkaline products Remove stains im...

Страница 9: ...eport N 2300800CDG 001 controlled by INTERTEK Laboratory inc CSA C22 2 No 236 issue 2011 10 14 Ed 4 Heating and Cooling Equipment report N 2300800CDG 001 controlled by INTERTEK Laboratory inc CEM elec...