background image

PART IV: MAINTENANCE

40

8.6  Replacing the detection electrode

To replace the detection electrode, proceed as follows:
1

remove the combustion head according to the procedure on paragraph “Removing the combustion head”;

2

by means of an allen key, loose the fixing screws of the detection electrode 

ER

 and replace it;

3

replace the combustion head.

8.7  Checking the detection current (natural gas)

To check the detection signal follow the scheme in the picture below. If the signal is less than the value indicated, check the position of

the detection electrode or detector, the electrical contacts and, if necessary, replace the electrode or the detector.

8.8  Checking the detection current (L.P.G.)

To check the detection signal follow the scheme in the picture below. If the signal is less than the value indicated, check the position of

the detection electrode or detector, the electrical contacts and, if necessary, replace the electrode or the detector.

ATTENTION: avoid the electrode to get in touch with metallic parts (blast tube, head, etc.), otherwise the boiler
operation would be compromised. Check the electrode position after any intervention on the combustion head. 

Device

Flame detector

Minimum detection signal

Siemens LMV2x/3x

Ionization probe

4 µA (values on display: 30%)

Device

Flame detector

Minimum detection signal

Siemens LMV2x/3x

QRA

70 µA  (intensity of flame >24%)

ER

ER

Protective earth PE

Ionization probe (ION)

QRB.../ QRC... signal voltage

QRB... GND

1

2

3

4

5

L

X10-05

 

 

QRA... (-)

QRA... (+)

1

2

X10-06

+

 

Содержание R512A L Series

Страница 1: ...M039240CC 2 5 03 2015 BURNERS BRUCIATORI BRULERS BRENNER QUEMADORES LMV2x 3x Microprocessor controlled gas burners MANUAL OF INSTALLATION USE MAINTENANCE R91A R92A R93A R512A R515A R520A R525A...

Страница 2: ...CTIONS FOR BURNERS z The burner should be installed in a suitable room with ventilation openings complying with the requirements of the regulations in force and sufficient for good combustion z Only b...

Страница 3: ...ditions such as the development of toxic or explosive mixtures DIRECTIVES AND STANDARDS Gas burners European directives Directive 2009 142 EC Gas Appliances Directive 2006 95 EC on low voltage Directi...

Страница 4: ...apparatus EN 50165 Electrical equipment of non electric appliances for household and similar purposes Safety requirements UNI EN 746 2 Industrial thermoprocessing equipment Burner data plate For the...

Страница 5: ...one for ces the pressure in the utilisation limits The actuators move proportionally the air damper and the gas butterfly valve in order to achieve the optimisation of the gas flue values as to get a...

Страница 6: ...micro processor control without inverter EB micro processor control with inverter BURNER TYPE R91A M R92A M R93A M Output min max kW 480 2670 480 3050 550 4100 Fuel M Natural gas Category see next pa...

Страница 7: ...t min max kW 600 4500 770 5200 1000 6400 2000 6700 2000 8000 Fuel M Natural gas Category see next paragraph Gas rate Natural gas min max Stm3 h 63 476 81 550 106 677 212 709 212 847 PressureGas pressu...

Страница 8: ...in 65 Valves size Gas connection 65 DN65 65 DN65 65 DN65 65 DN65 Gas train 80 Valves size Gas connection 80 DN80 80 DN80 80 DN80 80 DN80 Gas train 100 Valves size Gas connection 100 DN100 100 DN100 10...

Страница 9: ...441 866 421 1406 971 435 269 299 228 447 360 464 M12 424 280 310 300 632 148 484 846 292 649 228 185 R92A 80 1356 242 35 579 132 490 441 866 421 1437 1002 435 269 299 228 447 360 464 M12 424 280 310 3...

Страница 10: ...145 530 517 969 446 1726 1082 644 380 420 494 540 494 M14 552 390 390 791 149 642 942 353 764 316 270 R520A 50 1499 320 35 595 100 530 517 969 446 1590 946 644 400 440 494 540 604 M14 552 390 390 763...

Страница 11: ...o the available gas pressure value upstream the burner s gas valve Then subtract the backpressure The result is called pgas Draw a vertical line matching the furnace input value 600kW in the example q...

Страница 12: ...is set in order to find a compromise between the burner output and the generator specifications that is why the minimum output may be different from the Per formance curve minimum BACK PRESSURE IN COM...

Страница 13: ...R520A M Stm3 h GAS PRESSURE mbar R525A M Rp2 Stm3 h R525A M DN65 80 100 Stm3 h Caution the gas rate value is quoted on the x axis the related network pressure is quoted on the y axis pressure value in...

Страница 14: ...3 h GAS PRESSURE mbar R520A L Stm3 h Caution the gas rate value is quoted on the x axis the related network pressure is quoted on the y axis pressure value in the combustion chamber is not included To...

Страница 15: ...the combustion chamber 3 Gas pressure outlet on the butterfly valve 4 Differential pressure gauge 2 10 Measuring the gas pressure in the combustion head In order to measure the pressure in the combust...

Страница 16: ...0 100 120 140 160 180 200 220 240 260 280 300 0 5 10 15 20 25 30 35 40 45 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 340 0 5 10 15 20 25 30 35 40 45 50 50 75 100 125 150 175 200 225 250...

Страница 17: ...Stm3 h R93A L Stm3 h Gas pressure in combustion head R512A L Stm3 h GAS PRESSURE mbar R520A L Stm3 h 0 2 4 6 8 10 12 14 16 18 20 22 24 26 10 20 30 40 50 60 70 80 90 100 110 0 10 20 30 40 50 60 70 10...

Страница 18: ...llowing are placed in each packing case z burner with detached gas train z gasket or ceramic fibre plait according to burner type to be inserted between the burner and the boiler z envelope containing...

Страница 19: ...In case the burner must be coupled with boilers with a combustion chamber smaller in dia meter or shorter than those described in the diagram please contact the supplier to verify that a correct match...

Страница 20: ...tes the utilisation please contact the manifacturer Fig 3 Key a Heat output in kW b Lenght of the flame tube in meters c Flame tube firing intensity in MW m3 d Combustion chamber diameter m Fig 3 Firi...

Страница 21: ...ets are not part of the standard supply ATTENTION BEFORE EXECUTING THE CONNECTIONS TO THE GAS PIPE NETWORK BE SURE THAT THE MANUAL CUTOFF VALVES ARE CLOSED Gas train with valves group VGD with built i...

Страница 22: ...tted z Connect the reference gas pipe TP in figure 8mm external size pipe supplied loose to the gas pressure nipples placed on the gas pipe downstream the gas valves gas pressure must be measured at a...

Страница 23: ...pressure Test atmospheric pressure EV1 closes and keep this position for a preset time test time td1 The pressure switch PGCP has not to detect a rise of pressure z Test space filling EV2 opens and k...

Страница 24: ...terminal X3 04 4 in case of LMV2x LMV3x LMV5x LME7x on the board and the earth terminal an RC Siemens RC466890660 filter must be inserted For LMV5 control box please refer to the clabeling recommendat...

Страница 25: ...VER OPEN OR DISMANTLE ANY COMPONENT OF THE MACHINE EXCEPT FOR ITS MAINTENANCE TO SECURE THE MACHINE ACT ON THE ISOLATOR SWITCH IN CASE OF ANOMALIES THAT REQUIRED A SHUT DOWN OF THE BURNER IT S POSSIBL...

Страница 26: ...the gas pressure is sufficient signalled by an error code on the AZL display z At the beginning of the start up cycle the actuator drives the air damper to the maximum opening position then the fan m...

Страница 27: ...me output increasing too much or that the flues temperature gets too low to cause condensation in the chimney 7 2 User interface The AZL2x display is shown below The keys functions are the following W...

Страница 28: ...Serivce during the curve adjustments Key Used to increase a a value Used to enter Info and Serivce during the curve adjustments Keys ESC By pressing and at the same time the ESCAPE function is perfome...

Страница 29: ...asformatore accen sione ON TSA1 1st safety time ignition transformer ON Ph42 TSA1 primo tempo sicurezza trasformatore accen sione OFF TSA1 1st safety time ignition transformer OFF t42 preignition time...

Страница 30: ...splay will show InFo Press the enter InFo key 3 then il will show the first code 167 flashing on the right side it will show the data entered By pressing or it is possible to scroll up or down the par...

Страница 31: ...or by pressing ESC or InFo for more seconds the display will show 9 Once the last parameter is accessed 143 by pressing the End message will flash 10 Press InFo for more than three seconds or for mor...

Страница 32: ...the reset press InFo for one second The unit displays an event which does not lead to shutdown The display shows current error code c alternating with diagnostic code d Press InFo to return to the dis...

Страница 33: ...ner control panel see next picture instead of the TAB thermo stat as described on the previous paragraphs about the progressive burners Go on adjusting the burner as described before paying attention...

Страница 34: ...Slowly fully open the manual cutoff valve z Refit the transparent plastic cover on the pressure switch 7 7 Adjusting the maximum gas pressure switch when provided To calibrate the maximum pressure sw...

Страница 35: ...n head towards the MIN position by turning clockwise the VRT ring nut Fasten VB screw when the adjustment is accomplished 7 11 Center head holes gas flow regulation natural gas burners To adjust the g...

Страница 36: ...on the adjusting plate notches and let it move CW CCW as to open close the holes 3 once the adjustmet is performed fasten the V screws The adjusting plate correct position must be regulated in the pla...

Страница 37: ...ollows 1 remove the cap unscrewing the fixing screws A 2 remove the filtering cartridge B clean it using water and soap blow it with compressed air or replace it if necessary 3 replace the cartridge i...

Страница 38: ...e described above having care to place correctly the O ring OR between burner and gas manifold To replace the spring in the gas valve group proceed as follows 1 Carefully twist the protection cap 1 an...

Страница 39: ...ack to the outside and remove the combustion head D 6 loose the screw of th eignition electrodes support E 7 remove the electrodes and replace them paying attention to the measures showed in figure F...

Страница 40: ...etector 8 8 Checking the detection current L P G To check the detection signal follow the scheme in the picture below If the signal is less than the value indicated check the position of the detection...

Страница 41: ...proceed as follows 1 turn the burner main switch to 0 Off position 2 disconnect the power mains 3 close the fuel valve of the supply line 8 10 Burner disposal In case of disposal follow the instructio...

Страница 42: ...MAINTENANCE 42 9 0 WIRING DIAGRAMS Refer to the attached wiring diagrams WARNING 1 Electrical supply 230V 50Hz 1 a c 400V 50Hz 3N a c 2 Do not reverse phase with neutral 3 Ensure burner is properly e...

Страница 43: ...AS z z MAXIMUM GAS PRESSURE SWITCH DEFECTIVE z z THERMOSTATS PRESSURE SWITCHES DEFECTIVES z z z OVERLOAD TRIPPED INTERVENTION z AUXILIARIES FUSE INTERRUPTED z DEFECTIVE CONTROL BOX z z z z z DEFECTIVE...

Страница 44: ...B A C B 11 2 11 3 1 2 6 7 2 6 13 6 5 9 2 9 3 3 4 1 1 4 1 2 7 3 1 7 4 6 1 6 1 1 6 2 10 2 5 11 6 1 8 1 6 7 1 9 1 4 1 3 12 2 11 5 6 3 14 2 5 14 2 4 15 13 1 13 2 8 2 6 4 7 3 4 7 1 7 2 12 1 14 1 14 2 3 11...

Страница 45: ...2 5 CONTROL PANEL 4 2 BUTTERFLY GAS VALVE 9 2 COUPLING 15 BRACKET 5 IGNITION CABLE 9 3 BRACKET 16 DETECTION CABLE 6 1 BURNER HOUSING 10 1 FAN WHEEL 6 1 1 COVER 10 2 MOTOR 6 2 INSPECTION GLASS 11 1 DE...

Страница 46: ......

Страница 47: ......

Страница 48: ...ia L Galvani 9 35011 Campodarsego PD ITALY Tel 39 049 9200944 Fax 39 049 9200945 9201269 web site www cibunigas it e mail cibunigas cibunigas it Note specifications and data subject to change Errors a...

Отзывы: