EN-85
EREBA He
Par.
CIAT
Jbus
Mnemonic
Description
Range
Default
Unit
WUI
Table
222
ms_cap
Mast/Slv Total Capacity
0 to 100
0
%
RO
RO
MSL_STAT
223
Mst_req
Master Request Capacity
0 to 100
0
%
RO
RO
MSL_STAT
224
slv1_req
Slave #1 Request Capa.
0 to 100
0
%
RO
RO
MSL_STAT
225
slv2_req
Slave #2 Request Capa.
0 to 100
0
%
RO
RO
MSL_STAT
226
slv3_req
Slave #3 Request Capa.
0 to 100
0
%
RO
RO
MSL_STAT
228
5062H
ms_activ
Mast/Slv Active Flag
False/True
False
-
RO
RO
MSL_STAT
229
MS_STAT
Mast/Slv Overall Status
-1 to 109
0
-
RO
RO
MSL_STAT
230
mast_sta
Master Status
-1 to 109
-
RO
RO
MSL_STAT
231
slv1_sta
Slave #1 Status
-1 to 109
-
RO
RO
MSL_STAT
232
slv2_sta
Slave #2 Status
-1 to 109
-
RO
RO
MSL_STAT
233
slv3_sta
Slave #3 Status
-1 to 109
-
RO
RO
MSL_STAT
234
MS_LIM
Mast/Slv Demand Limit
0 to 100
0
%
RO
RO
MSL_STAT
241
pool_ovr
Pool Heating Override
-1 to 100
-
RO
RO
POOLSTAT
242
pool_dem
Pool Heating Demand
0 to 1
-
RO
RO/F
POOLSTAT
243
poolcond
Pool Heating Conditions
0 to 1
-
RO
RO/F
POOLSTAT
244
POOL_EWT
Pool Entering Water Temp
-40 to 115,6
1/10°C
RO
RO/F
POOLSTAT
245
POOL_EXC
Pool Exception Timer
0 to 1140
min
RO
RO/F
POOLSTAT
246
POOL_VLV
Pool Diverting Valve
0 to 1
-
RO
RO/F
POOLSTAT
247
POOL_RUN
Pool Heating Run Status
0 to 1
-
RO
RO/F
POOLSTAT
248
Pool Heating Runtime
-
RO
RO/F
POOLSTAT
301
model
Inverter Model
-
RO
RO
Inverter
302
prg_ver
Inverter Progr Version
-
RO
RO
Inverter
303
prg_rev
Inverter Progr Revision
-
RO
RO
Inverter
304
eep_cod
Inverter EEPROM Code
-
RO
RO
Inverter
305
sw_set
Inverter Switch Setting
-
RO
RO
Inverter
306
cdu_cap
CDU Capacity
0 to 15
-
RO
RO
Inverter
307
mcu_code
MCU Code
-
RO
RO
Inverter
308
cdu_amp
CDU Current
mA
RO
RO
Inverter
311
def_ovr
Defrost Override
-4 to 32
0
-
DEF_STAT
312
def_dt0m
Ref Defrost DeltaT (MD)
0 to 30
-
K
DEF_STAT
313
DEF_DT0
Ref Defrost DeltaT
0 to 30
-
K
DEF_STAT
314
def_dt
Actual Defrost DeltaT
K
DEF_STAT
315
def_fact
Frost Factor
%
DEF_STAT
316
def_nb
Free Defrost sessions number
0
-
DEF_STAT
317
def_time
Free Defrost duration
s
DEF_STAT
318
md_last
Time since last MD
min
DEF_STAT
319
fd_last
Time since last FD
min
DEF_STAT
321
QCK_ENA
QT: Quick Test enable
0/1 [No/Yes]
-
RW
RW/F
QCK_TEST
322
_HP_TEST
QT: HP Switch Test
N,A,
-
RW
RW/F
QCK_TEST
323
_RAT_MOD
QT: Rating Mode
0 to 4 [Rating Off/ Rating
Cool/ Rating Heat/ Ramp
Cool/ Ramp Heat]
-
RW
RW/F
QCK_TEST
324
_RAT_FRQ
QT: Rating Frequency
0 to 120
1/10 Hz
RW
RW/F
QCK_TEST
325
_FAN_LOW
QT: Lower Fan Speed
0 to 1000
rpm
RW
RW/F
QCK_TEST
326
_FAN_UPP
QT: Upper Fan Speed
0 to 1000
rpm
RW
RW/F
QCK_TEST
327
_PMV_POS
QT: PMV Position
0 to 1000
-
RW
RW/F
QCK_TEST
331
_PMP
QT: Water Pump Speed
0 to 100
%
RW
RW/F
QCK_TEST
332
_ADD_PMP
QT: Additional Pump
0/1 [Off/On]
-
RW
RW/F
QCK_TEST
333
_EHS_PMP
QT: EHS Additional Pump
0/1 [Off/On]
-
RW
RW/F
QCK_TEST
334
_EXH_HTR
QT: Water Exchanger Heater
0/1 [Off/On]
-
RW
RW/F
QCK_TEST
335
_DHW_VLV
QT: DHW Diverting Valve
0/1 [Off/On]
-
RW
RW/F
QCK_TEST
336
_BOILER
QT: Boiler or EHS1
0/1 [Off/On]
-
RW
RW/F
QCK_TEST
310
_CUSTDO5
QT: Customized DO#5
0/1 [Off/On]
-
RW
RW/F
QCK_TEST
337
_CUSTDO8
QT: Customized DO#8
0/1 [Off/On]
-
RW
RW/F
QCK_TEST
338
_CUSTDO9
QT: Customized DO #9
0/1 [Off/On]
-
RW
RW/F
QCK_TEST
315
_CAP_OUT
QT: Capacity Output
0 to 100
0
%
RW
RW/F
QCK_TEST
340
51E6H
ALMRESET
Alarm Reset
0/1 [No/Yes]
-
RW
RW/F
ALARM
341
4E3EH
ALM
Alarm Status
0/1 [Normal/Alarm]
0
-
RO/d
RO
ALARM
342
4F02H
ALERT
Alarm Status
0/1 [No/Yes]
0
-
RO
RO
ALARM
343
4F04H
SHUTDOWN
Shutdown Status
0/1 [No/Yes]
0
-
RO
RO
ALARM
7 - PARAMETERS OVERVIEW