EN-33
EREBA He
3 - INSTALLATION OF SYSTEM
In this section, the general customer electrical connection is detailed as well as the main
steps of configuration and examples of standard installation:
- Installation with electrical booster heaters
- Installation with and boiler
- Master / Slave installation
Likewise the setpoint configuration with remote user interface is shown as well as the
installation of additional OAT sensor and IAT senor.
To obtain the list of all parameters, refer to §7.Parameter overview.
3.1 - General customer electrical connection on terminal block
Figure 10: Customer electrical connection on terminal block
All customer wiring and devices have to be field provided &
connected according to your system configuration.
DI#04- Safety Input Switch
CCN+ WUI CCN+ / B+
Ground CCN
CCN- WUI CCN - / B-
DI#01- O
ff
/On Switch (remote)
DI#02- Mode Cool/Heat (remote
DI#03- Normal/Eco (remote
DO#08- Customized
DO#09- Customized
DI#06- Customized
DI#07- Customized
DI#08- Customized
DI#05- Customized
Ground-Sensor [
Ω
]
AI#01- DHW Tank Temperature Sensor
AI#02- Chiller water System Temperature Sensor
AI#03- Indoor Air Temperature(Room Sensor)
AI#04- Outdoor Air Temperature Sensor
DO#06- DHW-V diver
ti
ng valve
DO#07- Electrical Heater EH#1/Boiler-On/O
ff
Neutral
WUI +12V
WUI 0V
DI's#- Ground
K001
A1
A2
Neutral
K002
A1
A2
K003
A1
A2
Func
ti
on
di1
di2
di3
di4
di6
di7
di8
Param.
Nb
DHW_TT
iat_type
CHWST
oat_type
P502
P503
P504
P505
di5
P506
P507
P511
P510
cust_do9
cust_do8
P501
cust_di5
cust_di6
cust_di7
cust_di8
sfsw_typ
P221
P206
1
2
3
4
5
6
7
9
10
11
12
13
13
13
13
14
15
16
17
Polarity
WUI(Remote)
12V
OV
B-
B+
24
25
CCN - Unit
1
2
3
18
18
19
20
21
22
23
23
23
24
25
29
32
33
34
35
36
37
38
Valve
Neutral
Addi
ti
onal Pump
Heater
Ground
JBUS +
JBUS Ground
JBUS -
DO#05 - Customized
Triac
230 VAC
RS485
In
resistance,
Ω
Dry contact
5V
Out 12 VAC
Relay
Out 230 VAC
PE
RS485
Relay
Dry contact
K004
A2
A1
P500
cust_do5
Note : See paragraph 7.2 for description of
customized DI/DO configurations