EREBA He
EN-20
2 - INSTALLATION OF UNIT
●
OAT sensor, located on the coil, should
not be exposed to the sun or other heat
sources.
Before lifting the unit, check that
all casing panels are securely fixed
in place. Lift and set down the unit
with great care. Tilting and jarring
can damage the unit and impair unit
operation.
If EREBA He units are hoisted with rigging, it
is advisable to protect coils against crushing
while a unit is being moved. Use struts or a
lifting beam to spread the slings above the
unit. Do not tilt a unit more than 15°.
Never push or lever on any of the
enclosure panels of the unit. Only
the base of the unit frame is designed
to withstand such stresses. If a unit
includes a hydraulic module, the
hydraulic module and pump piping
must be installed in a way that
does not submit it to any strain.
The hydraulic module pipes must
be fitted so that the pump does not
support the weight of the pipes.
2.2.3 - Removing the unit panel
To access at the inside of the unit (refrigerant parts / electrical parts), the panel can be
removed. This operation must be carried out by a qualified technician.
Figure 3 : How to remove front panel for 11 & 15 kW units
Figure 4 : How to remove front panel for 5 & 7 kW units