HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 14.712 A

Comfort units

Coanda effect cassette

i

ntegRation

 

in

 

sUspended

 

CeiLing

The air handling casing is fitted inside the suspended ceiling, in the centre of 4 tiles, to be positioned in the centre of the room. 

The COADIS LINE must be suspended from the ceiling using 4 threaded rods either 6 mm or 8 mm in diameter (not supplied), 

which are fixed to the unit's 4 support brackets using resilient mounts or a nut/washer assembly positioned on either side of the 

mounting bracket.

Suspended ceiling tile

Support brackets (x4)

Ø 100 mm fresh air inlet collar, max. 

air flow 90 m3/hr recommended.

Network balancing system 

(not supplied by CIAT)

Mounting principle 

2 options

Attached using 4 threaded rods  

(6mm or 8mm)

Resilient 

mount

Nut/washer 

assembly

Positioned either 

side of the 

mounting  

bracket

Coanda effect air diffusion

12.5

Содержание CDL922

Страница 1: ...ual 360 diffusion model Coanda effect diffuser across 360 The Coadis Line is available as A 2 tube system with heating or cooling mode A 2 tube 2 wire system with heating or cooling cooling electric m...

Страница 2: ...elected G3 EP EPURE filter G3 G3 filter HEE 2 10V Energy efficient motor 2 10V control HEE ON OFF Energy efficient motor 3 speed control AC 5 speed asynchronous motor 2000W For 922 3000W For 932 and 9...

Страница 3: ...on 80 C 2 tube application 70 C 2 tube 2 wire application 55 C min air flow rate 200m3 h min cold water inlet temperature 6 C Electric heater 2 tube electric system 230 1 50 single tube electrical ele...

Страница 4: ...cinerable at end of life Or flexible filter medium made of regenerative polyester fibre efficiency class EN 779 G3 fire rating M1 rigid metal frame accessible via the hinged air recovery grille Standa...

Страница 5: ...sing 4 threaded rods either 6 mm or 8 mm in diameter not supplied which are fixed to the unit s 4 support brackets using resilient mounts or a nut washer assembly positioned on either side of the moun...

Страница 6: ...g Unit Grid Total 922 35 10 45 924 35 45 932 40 50 932SP 40 50 934 40 50 934SP 40 50 900 240 103 5 75 27 205 67 60 40 145 32 S1 S E1 E 981 938 21 5 G1 2 heating manifold G3 4 cooling manifold Condensa...

Страница 7: ...Valve and motor assembly 24V or 230V Heating cooling assembly for valves with 3 point motors Heating cooling assembly for valves with thermo actuators PN16 15 230Vac 230Vac PN16 15 Outlet O ring O ri...

Страница 8: ...ew European ErP Energy related Products directive applies to all manufacturers of equipment fitted with a fan with a power input of between 125 watts and 500 kilowatts inclusive in this directive the...

Страница 9: ...tube system Hot or cold water coil G3 4 G3 4 G3 4 4 tube system Cold water coil G3 4 G3 4 G3 4 Hot water coil G1 2 G1 2 G1 2 Condensate drain pump TECHNICAL CHARACTERISTICS Maximum flow rate 100 l h...

Страница 10: ...XB Bornier de raccordement Terminal block Note Commande du ventilateur si gestion 0 10V thermostat client Fan control if 0 10V control customer s thermostat Condensate drain pump wiring Vert Jaune Gre...

Страница 11: ...s box side Code Serial number Description of the unit Rated motor output Motor rotation speed Coil type Wiring diagram reference Motor speed wiring Maximum service pressure Electric heater specificati...

Страница 12: ...peed selection With 0 10 V control adjustment via the controller with 3 speed on off control adjustment via the control unit option Note For more information refer to instruction manual N11 47 speed s...

Страница 13: ...2000 W 2R 5 4 V4 990 5 570 4 460 7 240 49 31 6 0 V3 845 4 990 3 960 6 460 46 28 7 0 V2 700 4 320 3 400 5 590 43 24 8 5 V1 550 3 610 2 760 4 620 40 20 10 8 932 V5 1090 7 600 5 690 9 030 50 33 3000 W 3...

Страница 14: ...00W 3000W Size 922 932 932SP 922 932 932SP Air handling section auxiliary pan Code 7344019 7344020 7351396 7344013 7344014 7351314 Diffusion interface VISUAL 360 with EPURE filter Code 7335537 VISUAL...

Страница 15: ...d flexible connections EPDM pipe PN10 stainless steel braid length 300 mm Female rotary couplings on both sides Code 2 x 5202298 All 2 way valve Two M1 9 mm thick insulated flexible connections EPDM p...

Страница 16: ...the unit or open the suspended ceiling Smooth and free from corners where dust could accumulate the single slot diffusion system enables quick easy cleaning The VISUAL 360 interface will be primarily...

Страница 17: ...leaks for electrical safety and for the proper protection of components The fresh air enters through a smooth metal sleeve with no flow control or via a self adjusting collar and module assembly desig...

Отзывы: