background image

3

CO

ADIS LINE 900

HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 14.712 A

Comfort units

Coanda effect cassette

t

eChniCaL

 

desCRiption

Return/supply air interface

●  VISUAL 360°

Painted galvanised steel.

  PSE insulation, 10 to 40 mm thick.

  Uniform RAL 9010 white colour for all components. Integration 

within a suspended ceiling, fitting in the centre of four tiles.

  Perforated metal return air grille with filter housing with quick 

opening via 2 lugs.

  Interface secured by 4 screws, to be removed to gain full 

access to the internal components (coil, FMA, temperature 

limiters, condensate pan, condensate drain pump).

 Coanda effect diffusion which allows a jet of air to follow the 

ceiling, preventing cold air from dropping into the comfort area. 

Coanda effect offers 360° coverage of the surface area of the 

room to be treated, with no dead zone.

  Narrow opening single-slot and specific internal profile.

Base

 

  Ribbed galvanised steel motor support base panel.

 

   High-density PSE packaged casing, ensuring the thermal 

and acoustic functionalities. 18 mm thick for the base and 

25 mm to 30 mm thick for the vertical walls which form the 

casing. M1 fire rating.

 

   Low emission of TVOCs and no halogenated compounds.

 

   ABS technical plate supporting the electrics box, hydraulic 

and air couplings (fresh air).

 

 

 

 

Reinforcing ABS angle bars fitted in the corners and 

equipped with open galvanised steel mounting brackets with 

check valve for fitting threaded rods.

 

   Fixed frame in RAL 9010 painted (white) galvanised steel, 

housing the return/supply air interface and providing rigidity 

to the casing assembly.

Water coil

●   1 hot water or cold water circuit (2-tube system),

●   1 hot water + 1 cold water circuit (4-tube system),

●   one-piece  coupling  (40  mm  centre  distance)  with  rotating 

female couplings with integrated flat face and seals, for easy 

fitting of control valves,

●   one, two or three-row circular coil with low pressure drop,

●   copper tubes, continuous aluminium fins (1.8 mm spacing),

●   bleeding and draining,

●   nominal pressure of 16 bar (at 20°C),

●   test pressure of 24 bar,

●   max. hot water inlet temperature:

- 4-tube application: 80°C,

- 2-tube application: 70°C,

- 2-tube/2-wire application: 55°C (min. air flow rate: 200m3/h)

●   min. cold water inlet temperature: 6°C.

Electric heater 
(2-tube + electric system)

230/1/50 single-tube electrical elements inserted into the 

aluminium housing.

Two temperature limiters with manual and automatic reset, 

inserted into the aluminium housing and easily accessible via 

the return/supply air interface without the need to open the 

suspended ceiling.

Heater power supply connected to the terminal block inside 

the electrics box.

Option of deactivating a heater on site by removing a shunt 

from the terminal block, to reduce the electrical power.

Condensate drain pan

One-piece main pan with all-climate insulation in high-density 

PSE, with sealing treatment on the upper section.

   Removable  from  below.

   Condensate drainage (internal Ø 32 connection) provided by 

an internal drain pump equipped with a safety float, check 

valve and fitted on anti-vibration mounts.
Auxiliary pan available as an accessory for recovery of 

condensate from the valves.

Fan motor assembly

 HEE motor

High energy efficiency motor enabling a reduction of up to 

85% in electricity consumption.

●  BLAC  (Brushless  Alternating  Current)  technology  offering 

more linear torque progression and a lower operating sound 

level than BLDC (Brushless Direct Current) technology,

●  sealed, tropicalised, with protected shaft,

●  3-speed gradual operation by 0-10V or on/off control signal, 

without expansion board,

● ball bearings,

●  internal  automatic  overload  protection  as  standard  on 

winding,

●  "DFS" motor fault output using a photocoupler for potential 

alarm feedback via a Konnex protocol communication bus 

(via the V3000 controller)

,

●  fitted on anti-vibration mounts,

●   230V/1Ph/50 Hz power supply (60Hz compatible).

Note: The minimum voltage required for start-up of the motor 

is 2V.

Or

■ 

Asynchronous motor

5 factory-fitted cabled speeds (connected and available at the 

terminal) for customised adjustment.

●  sealed, tropicalised, with protected shaft,

●  permanent capacitor,

●  ball bearings,

●  internal  automatic  overload  protection  as  standard  on 

winding,

●  resilient mounts,

●  230V/1Ph/50 Hz power supply (60Hz compatible),

●  high efficiency and power factor.

■ 

Fan(s)

●  balanced centrifugal impeller (Ø 476mm) with airfoil blades,

●  polymer impeller,

●  single-point mounting system with foolproofing device.

Содержание CDL922

Страница 1: ...ual 360 diffusion model Coanda effect diffuser across 360 The Coadis Line is available as A 2 tube system with heating or cooling mode A 2 tube 2 wire system with heating or cooling cooling electric m...

Страница 2: ...elected G3 EP EPURE filter G3 G3 filter HEE 2 10V Energy efficient motor 2 10V control HEE ON OFF Energy efficient motor 3 speed control AC 5 speed asynchronous motor 2000W For 922 3000W For 932 and 9...

Страница 3: ...on 80 C 2 tube application 70 C 2 tube 2 wire application 55 C min air flow rate 200m3 h min cold water inlet temperature 6 C Electric heater 2 tube electric system 230 1 50 single tube electrical ele...

Страница 4: ...cinerable at end of life Or flexible filter medium made of regenerative polyester fibre efficiency class EN 779 G3 fire rating M1 rigid metal frame accessible via the hinged air recovery grille Standa...

Страница 5: ...sing 4 threaded rods either 6 mm or 8 mm in diameter not supplied which are fixed to the unit s 4 support brackets using resilient mounts or a nut washer assembly positioned on either side of the moun...

Страница 6: ...g Unit Grid Total 922 35 10 45 924 35 45 932 40 50 932SP 40 50 934 40 50 934SP 40 50 900 240 103 5 75 27 205 67 60 40 145 32 S1 S E1 E 981 938 21 5 G1 2 heating manifold G3 4 cooling manifold Condensa...

Страница 7: ...Valve and motor assembly 24V or 230V Heating cooling assembly for valves with 3 point motors Heating cooling assembly for valves with thermo actuators PN16 15 230Vac 230Vac PN16 15 Outlet O ring O ri...

Страница 8: ...ew European ErP Energy related Products directive applies to all manufacturers of equipment fitted with a fan with a power input of between 125 watts and 500 kilowatts inclusive in this directive the...

Страница 9: ...tube system Hot or cold water coil G3 4 G3 4 G3 4 4 tube system Cold water coil G3 4 G3 4 G3 4 Hot water coil G1 2 G1 2 G1 2 Condensate drain pump TECHNICAL CHARACTERISTICS Maximum flow rate 100 l h...

Страница 10: ...XB Bornier de raccordement Terminal block Note Commande du ventilateur si gestion 0 10V thermostat client Fan control if 0 10V control customer s thermostat Condensate drain pump wiring Vert Jaune Gre...

Страница 11: ...s box side Code Serial number Description of the unit Rated motor output Motor rotation speed Coil type Wiring diagram reference Motor speed wiring Maximum service pressure Electric heater specificati...

Страница 12: ...peed selection With 0 10 V control adjustment via the controller with 3 speed on off control adjustment via the control unit option Note For more information refer to instruction manual N11 47 speed s...

Страница 13: ...2000 W 2R 5 4 V4 990 5 570 4 460 7 240 49 31 6 0 V3 845 4 990 3 960 6 460 46 28 7 0 V2 700 4 320 3 400 5 590 43 24 8 5 V1 550 3 610 2 760 4 620 40 20 10 8 932 V5 1090 7 600 5 690 9 030 50 33 3000 W 3...

Страница 14: ...00W 3000W Size 922 932 932SP 922 932 932SP Air handling section auxiliary pan Code 7344019 7344020 7351396 7344013 7344014 7351314 Diffusion interface VISUAL 360 with EPURE filter Code 7335537 VISUAL...

Страница 15: ...d flexible connections EPDM pipe PN10 stainless steel braid length 300 mm Female rotary couplings on both sides Code 2 x 5202298 All 2 way valve Two M1 9 mm thick insulated flexible connections EPDM p...

Страница 16: ...the unit or open the suspended ceiling Smooth and free from corners where dust could accumulate the single slot diffusion system enables quick easy cleaning The VISUAL 360 interface will be primarily...

Страница 17: ...leaks for electrical safety and for the proper protection of components The fresh air enters through a smooth metal sleeve with no flow control or via a self adjusting collar and module assembly desig...

Отзывы: