13
CO
ADIS LINE 900
HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 14.712 A
Comfort units
Coanda effect cassette
p
eRfoRmanCe
Operation, 2-tube system
Summer: cold water inlet 7/12°C, air 27°C WB 19°C.
Winter: hot water inlet 50°C for water flow rate identical to summer mode, air 20°C.
Operation, 4-tube system
Summer: cold water inlet 7/12°C, air 27°C WB 19°C.
Winter: hot water inlet 70/60°C, air 20°C.
Comfort level: attenuation level of the space and installation: 12 dB.
* The values are given for information purposes and may be changed at a later date.
COADIS LINE
900
Motor code
Air flow m
3/h
2-tube system and 4-tube system
LW
dB (A)
Comfort level
(ISO or NR)
Average air temperature rise
in K
Auxiliary electric heater 230/1/50
Cooling power (W)
Heating
capacity (W)
Total
Sensible
2R or 3R
922
V5
1100
6 060
4 890
7 760
51
33
2000 W (2R)
5.4
V4
990
5 570
4 460
7 240
49
31
6.0
V3
845
4 990
3 960
6 460
46
28
7.0
V2
700
4 320
3 400
5 590
43
24
8.5
V1
550
3 610
2 760
4 620
40
20
10.8
932
V5
1090
7 600
5 690
9 030
50
33
3000 W (3R)
8.2
V4
985
6 980
5 190
8 240
48
32
9.0
V3
850
6 130
4 510
7 220
44
26
10.5
V2
710
5 210
3 800
6 100
41
22
12.5
V1
570
4 230
3 070
4 910
37
18
15.6
932SP
V5
1420
9 350
7 210
11 200
59
42
3000 W (3R)
6.3
V4
1325
8 860
6 770
10 600
56
39
6.7
V3
1225
8 330
6 310
9 940
54
37
7.3
V2
1120
7 770
5 840
9 250
51
34
8.0
V1
1020
7 170
5 340
8 500
48
32
8.7
924
V5
1100
6 060
4 900
4 110
51
33
V4
990
5 570
4 470
3 880
49
31
V3
845
4 990
3 970
3 590
46
28
V2
700
4 320
3 410
3 250
43
24
V1
550
3 610
2 770
2 870
40
20
934
V5
1090
7 600
5 710
5 090
50
33
V4
985
6 980
5 210
4 820
48
32
V3
850
6 130
4 530
4 410
44
26
V2
710
5 210
3 820
3 940
41
22
V1
570
4 230
3 080
3 400
37
18
934SP
V5
1420
9 350
7 230
5 720
59
42
V4
1325
8 860
6 790
5 570
56
39
V3
1225
8 330
6 330
5 390
54
37
V2
1120
7 770
5 860
5 160
51
34
V1
1020
7 170
5 360
4 900
48
32