29
3.2
Opening time adjustment (trimmer A) (ONLY PCM130)
3.3
Electronic clutch adjustment (trimmer A) (ONLY PCM100)
This adjustment works on the thrust force of geared-motor: this force must cause the moving of the
gate, and it’s closely dependent on the weight of its structure.
During the movement, also the gate acquires a thrust force.
Under provisions of the law, the adjustment must be made so that the thrust force of the gate is equal
to 15Kg; it means that a force equal to 15Kg, in opposition to the movement of the gate,
must stop the gate
during its movement.
To set this adjustment, we suggest you to use an instrument called
linear dynamometer
.
3.4
Time of pause adjustment (trimmer B)
If the central unit is setted on
Automatic operating
or
Automatic operating for Parks,
you
must adjust the time of pause that must elapse between the end of the opening and the start of
the closing of the gate.
3.5
Electronic Brake / Slowing Down (trimmer C) (ONLY
PCM100)
3.6
Control LEDs
Here's a summary of the signallings LEDs present on the board:
Turned in anticlockwise direction:
Electronic brake:
disabled
Slowing down:
e
nabled at the end of opening / closing
Turned in clockwise direction:
Electronic brake:
e
nabled, reduces the movement after the limit/stop is
activated.
Slowing down:
disabled
OFF
Photocell 1 engaged
STOP command active
Pulse on input A
(total opening)
Pulse on input B
(partial opening)
st/by
green
yellow
red
red
Photocell 2 engaged
st/by
red
red
Opening limit-stop
engaged
Closing limit-stop
engaged
green
Normal operating
Anomaly
green
BLINKING
ON
Anomaly
COLOR
st/by
/
/
/
/
st/by
st/by
st/by
st/by
/
/
/
Setup
28
PCM100 / PCM130 - User Manual
3.2.3
STEP-BY-STEP WITH AUTOMATIC RECLOSING
(SW1=OFF- SW2=ON)
One pulse allows : opening, pause, automatic closing
During opening and closing procedures, every pulse stops and reverse the movement of the
gate immediately.
During the pause, a pulse recloses the gate immediately.
3.2.4
MANUAL STEP-BY-STEP WITH STOP operating
(SW1=ON - SW2=ON)
One pulses opens; the next pulse stops; the next pulse closes ; the next pulse stops; the
next pulse opens, etc .
OPEN
IN PAUSE
CLOSING
The reclosing is stopped and at the end of the
pause, it restores other 5 sec. up to the reset
Stops operation and the gate opens immediately
IN STOP
Restarts the operating procedure before the
STOP (closing or opening)
The pulses A and B will be ignored.
The opening or closing operation are locked
GATE
STATUS
PULSE A
PULSE B
STOP
CLOSE
OPENING
Total Opening and
reclosing after the time
of pause
Stops operation
and switches to
STOP mode
No Effect
Partial Opening and
closing operation after
the time of pause
The opening is stopped and the next pulse
recloses the gate
Recloses the gate immediately
It is locked and only a new pulse recloses the
gate
STOP
CLOSING
Pulses A and B are ignored and all movement
are locked
Stops operation and the gate opens immediately
IN STOP
Restarts the operating procedure before the
STOP (closing or opening)
The pulses A and B will be ignored.
The opening or closing operation are locked
GATE
STATUS
PULSE A
PULSE B
STOP
CLOSE
OPENING
Total Opening
Stops operation
and switches to
STOP mode
No Effect
Partial Opening
The opening is stopped and the next pulse
recloses the gate
Reverses the movement of the motor
The closing is stopped and the next pulse
opens the gate
PHOTOCELL 1 PHOTOCELL 2
PHOTOCELL 1 PHOTOCELL 2
Disables A and B pulses
and disable opening
Disables A and B pulses
and disable opening
DIP1
ON
ON
See SWITCH 3 pages 9 and 10
See SWITCH 3 pages 9 and 10
LED
LED
FX30D
FX40D
FX30D
FX40D
FTC
LED Button P1
LED Button P2
LED photocell
1 status
LED photocell
2 status
LED opening
limit stop status
LED closing
limit stop status
LED STOP Status
LED microprocessor
diagnosis