CI Wireless Inc.
Description of the Control Module
MirrorCell Select CDR812 Manual
Rev. X1
6-13
6.11.6 Alarm Configuration
Each alarm source is associated with a specific configuration string. This string provides
the operator with the possibility to individually configure each alarm. The program has the
capability to enable or disable each alarm, the capability to disable the requirement to
acknowledge certain alarms (not including VLI, LGO, CLR, and ILI alarms), and the
capability to configure different thresholds for particular alarms.
The command to set the alarm string is:
SET
ALA [ALARMSOURCE] [ALARMSTRING] <enter>
The following tables describe the alarm string format and the default threshold values for
each of the alarms.
6.11.6.1 Alarm String Format
Field
Format
Description and Notes
Number
1
X
Determines if the alarm source is enable/disabled
X = 0 Alarm is enabled
X = 1 Alarm is disabled
2
Y
Determines whether the alarm needs acknowledgment
Y = 0 Alarm requires acknowledgment from the OMC
Y = 1 Alarm does not require acknowledgment from OMC
NOTE:
This attribute is not used by VLI, LGO, CLR, or ILI
3
E
Shows how alarm is to be calculated/measured
E = 1 Evaluate both thresholds
E = 2 Evaluate lower threshold
E = 3 Evaluate upper threshold
E = 4 Ignore limit thresholds (for digital signals such as
the door).
NOTE:
This attribute is only an indication of how the alarm
parameters are calculated. Changing this will not affect the
measurements; ie, the calculation is hard coded.
4
LLL
Lower threshold value
5
UUU
Upper threshold value
6
TTT
Time in seconds for the alarm/measurement to be out of
limits before an alarm is triggered.