6. Troubleshooting
Faults
Faults/Warning Faults icon
Alarm
Possible cause
Solution
code
F01
On constantly
Beep
continuously
Internal fault.
Please contact the distributor
or Service center.
F08
On constantly
Beep
continuously
Ensure that the UPS is not overloaded
and the ventilation opening is not blocked
and ambient temperature is not too high.
Wait for 10 minutes for the UPS to cool
down before turning it on again. If it does
not work. Please contact the distributor or
service center.
F02
On constantly
Beep
continuously
Internal fault.
Please contact the distributor
or Service center.
F03
On constantly
Beep
continuously
Internal fault.
Please contact the distributor
or Service center.
F05
On constantly
Beep
continuously
Internal fault.
Please contact the distributor
or Service center.
F06
On constantly
Beep
continuously
Internal fault.
Please contact the distributor
or Service center.
F07
On constantly
Beep
continuously
Overload fault
fault.
Reduce the member of loads
connected to the UPS.
F09
On constantly
Beep
continuously
The charger
of the UPS is
defective
Please contact the distributor
or Service center.
F11
On constantly
Beep
continuously
Overload fault
fault.
After confirm the equipment
safety, reset EPO
F04
On constantly
Beep
continuously
The UPS
output is
short
circuited
Turn off the UPS. Remove all loads.
Ensure that the loads are not failed or
the UPS has no internal short before turn
on it again. If failed, please contact the
distributor or service center.
Table 6-2 UPS troubleshooting of LCD panel indicator
Internal
overheat